remove the frost from the
evaporator to ensure efficient
system operation after a certain
time operation.
Heat pump units does not
start as soon as the system is
switched on.
This is normal phenomeno. To
protect the compressor from
frequent cycle, the heat pump
unit will not start within 3
minutes from last stop.
The heat pump fan stops
under high ambient
temperature.
This is normal phenomeno. The
fan will possibly stop to reduce
the evaporative pressur for
compressor protection under
high ambient temperature
operation.
12.3.
Other Phenomena-Abnormal
Phenomena
Possible Reason
Solutions
E
R
R
O
R
S
, P
LE
A
S
E
D
O
U
B
E
L C
H
E
C
K
B
E
FO
R
E
C
A
LL
S
E
R
V
IC
E
N
U
M
B
E
R
The central controller
displays “N/A” for some
paramters.
Communication is not
established successfully.
Please check the communication
cables between the central
controller controller and display,
among the heat pump units.
Heat pump units does not
start after the system is
switched on for a long time.
1.
Power supply error.
2.
Loose wiring.
3.
Bad fuse.
4.
Operation timer expired.
1.
Inspect the power supply.
2.
Inspect the wiring and fix.
3.
Replace the fuse.
4.
Check on the timer setting.
The circulation pump is
operating but with abnormal
noise.
1.
No water in piping
system.
2.
Air in pipin system.
3.
The valves are not fully
open.
4.
Blocked water filter.
1.
Inspect the water piping
system.
2.
Exhaust the air from the
piping system.
3.
Open all the valves fully.
4.
Clean the water filter.
Lower heating capacity and
the heat pump units are
always operating without
stop
1.
Bad insulation on water
side and high standby
loss.
2.
Bad performance of
ambient coil.
3.
Insufficient water.
4.
Small tank and the hot
water system is
undersized.
1.
Improve the water system
insulation.
2.
Inspect the air circulation
around the unit.
3.
Clean the water filter or
exhaust the gas in the system.
4.
Improve the system design by
inquiring
system
manufacturer.
Compressor does not start
1.
Bad compressor
contactor.
2.
Loose wiring.
3.
Compressor overload
protection.
1.
Replace the contactor.
2.
Inspect the wiring and fix.
3.
Check the UIM for error code.
4.
Reset the tank temperature.
5.
Clean the water filter or
Содержание CAHP-MC-38
Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS AIR TO WATER HEAT PUMP WATER HEATER CAHP MC 38 ...
Страница 6: ...2 Physical Dimensions Picture 2 1 Unit Dimensions ...
Страница 13: ...Picture 5 4b ...
Страница 14: ...Picture 5 4c ...
Страница 55: ...9 Appendix 12 4 Heat Pump Unit Wiring Diagram Picture 9 1 Heat Pump Unit Wiring Diagram ...
Страница 57: ...Picture 9 3 Incorrect Communication Cable Wiring ...