(2)
Low voltage cables requirement
There are many communication and signal cables in the hot water system. Please refer to table
5.7 for the detailed requirements on these cables.
Cable Description
Size
Standard
Length
Max.
Length
Remarks
The communication cable between
the central controller and the furthest
heat pump unit
2*1 mm
2
/
200m
Shielded cable
The communication cable between
the central controller and the heat
pump unit
2*1 mm
2
/
100m
Shielded cable
Tank temperature sensor cable
2*1 mm
2
20m
100m
Auxiliary heater temperature sensor
cable
2*1 mm
2
20m
100m
Auxiliary heater control cable
2*1.5mm
2
/
100m
Auxiliary heater flow switch cable
2*1.5 mm
2
/
100m
Shorted
if
the
auxiliary heater is
storage gas heater
Circulation pump control cable
1*1.5 mm
2
/
100m
Auxiliary heater pump control cable
1*1.5 mm
2
/
100m
Return water solenoid valve or pump
control cable
1*1.5 mm
2
/
100m
Table 5.7 Hot Water System Low Voltage Cables Requirement
(3)
Heat pump unit control box layout
Please refer to picture 5.7 for the control box layout of the heat pump unit.
Picture 5.7
(4)
Central controller installation
CAUTION:
Please connect the shielded wire of the communication cable to the ground, this will help to
improve the system anti-interference capability.
Содержание CAHP-MC-38
Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS AIR TO WATER HEAT PUMP WATER HEATER CAHP MC 38 ...
Страница 6: ...2 Physical Dimensions Picture 2 1 Unit Dimensions ...
Страница 13: ...Picture 5 4b ...
Страница 14: ...Picture 5 4c ...
Страница 55: ...9 Appendix 12 4 Heat Pump Unit Wiring Diagram Picture 9 1 Heat Pump Unit Wiring Diagram ...
Страница 57: ...Picture 9 3 Incorrect Communication Cable Wiring ...