1)
Please see picture 5.2 if the heat pump units are installed vertically.
Note: “FRONT” side is the side with the service panel.Please see picture 2.1 for details.
Picture 5.2
2)
Please see picture 5.3 if the heat pump units are installed horizontally.
Picture 5.3
3)
If the heat pump units are installed in the basement, or other closed spaces, please pay
attention to the air circulation of the space to make sure each unit has an air flow rate of
13,000 cubic meters per hour freely.
4)
The distance between the floor and the unit base needs to be kept higher than the maximum
snow or rain depth of the area, to avoid the units to be immersed by snow or rain.
1.6.
Unit Movement
1)
The heat pump units have been equipped with multiple protection packages. Please use
forklift, crane, to move them in the field. Please do not remove the package before the units
are located correctly.
2)
Please keep the heat pump units in horizontal status during the movement. The maximum
angle of inclination should be kept less than 30 degrees under extreme conditions to avoid
compressor damage. Please check the strength and the balance of the slings if the crane is
used. Please use four pieces of slings with diameters larger than 6mm and each sling should
be able to stand for six times of the heat pump unit weight.
Содержание CAHP-MC-38
Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS AIR TO WATER HEAT PUMP WATER HEATER CAHP MC 38 ...
Страница 6: ...2 Physical Dimensions Picture 2 1 Unit Dimensions ...
Страница 13: ...Picture 5 4b ...
Страница 14: ...Picture 5 4c ...
Страница 55: ...9 Appendix 12 4 Heat Pump Unit Wiring Diagram Picture 9 1 Heat Pump Unit Wiring Diagram ...
Страница 57: ...Picture 9 3 Incorrect Communication Cable Wiring ...