WATER HEATER INSTALLATION
WATER HEATER INSTALLATION
CONDENSATE DRAIN INSTALLATION
Installation must conform with these instructions and local building
codes.
Field supplied materials required for installation include:
•
Approved PVC cement and PVC primer.
•
1/2 inch PVC pipe - minimum length to equal the distance
between the water heater and a suitable building drain.
•
1/2 inch PVC fittings (elbows, couplings, and adapters)
necessary to install a condensate drain line between the Exhaust/
Condensate Elbow Assembly and a suitable building drain.
•
Floor mounted standoffs to brace the drain line.
INSTALLATION NOTES
1.
The condensate drains from the water heater’s covered by
this instruction have PH levels between 4.3 and 5.0. Install a
commercially available neutralizing kit if required by local codes.
Lower pH levels are acidic. Do not connect a metal condensate
drain line, such as copper pipe, to the water heater for this reason.
2.
The field installed condensate drain line must not be less than
1/2 inch PVC in size.
3.
THE EXHAUST ELBOW HAS A BUILT IN CONDENSATE
TRAP. DO NOT INSTALL AN ADDITIONAL TRAP IN THE
CONDENSATE DRAIN PIPING. DO NOT
remove, modify or
alter the factory condensate trap.
INSTALLATION INSTRUCTIONS
4.
Ensure the water heater’s Enable/Disable switch is in the
“Disable” position.
5.
Install a 1/2 inch PVC condensate drain line between condensate
drain connection on the Exhaust/Condensate Elbow and a
suitable building drain. The condensate line must slope to an
6.
Terminate the condensate drain piping with an elbow above the
drain. Ensure that any discharge will exit the condensate drain
line no more than 6 inches (15.2 cm) above a suitable building
drain, or external to the building. See
.
Note:
In cold climates it is recommended the condensate drain
be terminated at a suitable drain inside the building.
7.
Ensure the condensate drain line is not elevated above the
condensate drain connection on the Exhaust/Condensate Elbow.
.
8.
Brace the condensate drain line with floor-mounted standoffs
every three feet.
9.
Ensure that the condensate drains freely during start up. See
.
10.
Condensate clean out cap must be on and tight when unit is in
operation.
DRAIN LINE TO
TERMINATE NO
MORE THAN 6
INCHES (15.2 cm)
ABOVE DRAIN
BUILDING
DRAIN
1/2” NPT
CONDENSATE
DRAIN
CONNECTION
CONDENSATE
CLEANOUT
EXHAUST/CONDENSATE
(VENT) ELBOW
PRESSURE PORT
CONDENSATE DRAIN
LINE - FIELD
INSTALLED
Figure 42.
Condensate Drain Installation
GAS PIPING
Make sure gas supplied is same type listed on model rating plate. The
inlet gas pressure must not exceed 14 inch water column (3.5 kPa)
for natural and propane gas (L.P.). The minimum inlet gas pressure
shown on rating plate is that which will permit firing at rated input.
Schedule 40 Steel or Wrought Iron Pipe is the preferred material for
the gas line of this water heater. It is imperative to follow the sizing
recommendations in the latest version of the
Natural Gas and Propane
Code
if Corrugated Stainless Steel Tubing (CSST) is used as the gas
line for this water heater.
SEDIMENT TRAPS
Fire and Explosion Hazard
• Contaminants in gas lines can cause fire
or explosions.
• Clean all gas piping before installation.
• Install drip leg in accordance with
NFPA
54
or
CSA-B1491
.
A sediment trap shall be installed as close to the gas inlet of the
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nipple
in the bottom outlet or other device recognized as an effective
sediment trap.