9
Table 2.
TCapacity, Gas and Electrical Characteristics
Approximate Capacity
*Manifold Pressure
Electrical Characteristics
U.S. Gals.
Liters
Gas Type
“WC
kPA
Volts/Hz
Amperes
50
189
Nat./LP
0
0
120/60
<5
75
284
Nat/LP
0
0
120/60
<5
* The manifold pressure is the factory setting and is not adjustable. A negative pressure will be seen with just
the blower running without the Gas Control Valve open.
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Input
Recovery Capacities
Rating
(Btu/hr)
Rating
(kW)
Temp.
Rise
F
30
40
50
60
70
80
90
100
110
120
130
140
C
17
22
28
33
39
44
50
56
61
67
72
78
100,000
29.3
GPH
387
291
233
194
166
145
129
116
106
97
90
83
LPH
1465
1102
882
734
628
549
488
439
401
367
341
314
Recovery capacity based on 96% thermal efficiency.