 Cold Shrink Integrated Splice 

Kit QS-III 5458A-IJ

for Jacketed Concentric Neutral (JCN) Cable
Instructions

IEEE Std. 404

25/28 kV Class

200 kV BIL

 

CAUTION

 

 Working around energized systems may cause serious injury or death. Installation should 

be performed by personnel familiar with good safety practice in handling electrical 

equipment. De-energize and ground all electrical systems before installing product.

Kit Selection Table

Kit Number

Cable Insulation O.D. Range

Conductor Size Range

5458A-IJ

1.24"–2.07"

(31,5–52,6 mm)

500–1000 kcmil*

(240–500 mm

2

)

* Splices (including size transitions) can be made to smaller or larger conductors (but larger conductors may require special neutral 

handling), provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements 
shown below.

Connector Dimensional Requirements

Minimum Inches (mm)

Maximum Inches (mm)

Outside Diameter

1.05" (26,7 mm)

2.07" (52,6 mm)

Length

Aluminum (Al/Cu) Compression

7.50" (191 mm)

Length

Copper Compression  and 
3M

 Shearbolt Connector QCI 500-1000

8.25" (210 mm)

September

 

2010

78-8127-8872-3-

B

3

Содержание 5458A-IJ

Страница 1: ... Cable Insulation O D Range Conductor Size Range 5458A IJ 1 24 2 07 31 5 52 6 mm 500 1000 kcmil 240 500 mm2 Splices including size transitions can be made to smaller or larger conductors but larger conductors may require special neutral handling provided both cables are within the Insulation O D Range and the connector meets the dimensional requirements shown below Connector Dimensional Requiremen...

Страница 2: ...ld Shrink Adapter Tube 1 ea g 3M Cable Cleaning Pads CC 3 1 ea h Scotch Electrical Shielding Tape 24 1 x 15 1 ea i 3M Aluminum Foil Tape Strips 1115B 10 length 2 ea j Cut back Template 2 ea k Instruction Booklet 1 ea Cold shrink adapter tube may not be included in all kits Kits contain either 1 or 2 cut back templates as needed per conductor size Note Do not use knives to open plastic bags Note Co...

Страница 3: ...1 70 31 5 43 2 15 3 4 400 9 1 4 235 1000 500 1 59 2 07 40 4 52 6 15 1 4 387 mm 8 3 4 222 For 100 and 133 insulation levels Insulation OD is the final determining factor Cables must be within the Insulation OD Range of the splice kit and the connector must meet the dimensional requirements shown on the front page Figure 1 2 3 Carefully bend the cut neutral wires up and away from the cable semi con ...

Страница 4: ...ding Tape 24 Figure 3 2 5 Carefully lay neutral wires back down on top of the shielding tape and press into mastic Keep wire profile low by following the concentric turn in the cable Figure 4 2 6 Remove the liner from one 3M Aluminum Foil Tape Strip 1115B and secure the ends of the neutral wires Wrap the aluminum tape on top of itself and tightly press down on the edge of the tape toward the end o...

Страница 5: ...ket 30 760 mm from jacket edge on side where splice body will be parked 2 9 Slide integrated splice body onto clean cable jacket loose core end first Figure 6 Loose core end Integrated splice body Cleaned cable jacket Figure 6 3 0 Install Connector Note If using a crimp type connector go to step 3 3 3 1 If using a 3M Shearbolt Connector QCI 500 1000 refer to the instructions included with the conn...

Страница 6: ...n removal length shall not exceed 4 1 8 105 mm from conductor end Do not install connector now Figure 9 Note This assumes that the installer has determined the increased length of an aluminum connector crimped with a specific tool and die Aluminum Al Cu Crimp Connector Growth Chart Conductor Size Typical growth allowance per end 500 kcmil 1 4 6 mm 750 1000 kcmil 3 8 10 mm Note 1 Copper connectors ...

Страница 7: ...oper connector dimensions For standard 3M Connectors refer to table at the end of this instruction for crimping information Remove any excess oxidation inhibitor from connector ends if aluminum connector is used Figure 11 Connector Figure 11 4 0 Install Splice 4 1 Apply a tape marker to semi con insulation shield on cable which does not contain splice Measure 11 1 2 292 mm from center of connector...

Страница 8: ...sulation shield b Do not reduce cable insulation diameter below 1 24 31 5 mm specified for the splice c The insulation surface must be round smooth and free of cuts voids Sanding may be necessary finish sanding should be done with a 300 grit or higher electrical grade abrasive d Make certain that the cable insulation is smooth clean and dry before continuing 4 4 Apply red compound on cable insulat...

Страница 9: ... Counter clockwise Align splice body with tape marker Figure 15 5 0 Connect Shielding 5 1 Remove the vinyl tape holding the shield sleeve on the rejacketing tube and spread the shield sleeve out toward the cable jacket Note The 3M Cold Shrink Integrated Splice Body includes a pre installed ground braid for external grounding on either side of the splice body If not using the ground braid it may be...

Страница 10: ... circuit grounding is required at this location 6 1 Connect a ground wire to the pre installed ground braid on the integrated splice using an appropriate connector Keep connector profile as low as possible For C tap or H tap connectors position flat against the cable Crimp connector following the connector manufacturer s recommendations Figure 18 Ground Wire Connector Ground Braid Figure 18 ...

Страница 11: ...Ground Wire Ground Wire Rolled Mastic Half Mastic Strip Cable Jacket Rolled Mastic Half Mastic Strip Figure 19 6 3 Place the other half mastic strip over the previously applied mastic and ground wire Press the mastic around the ground wire and to the cable jacket Figure 20 Second Half Mastic Strip Ground Wire Figure 20 6 4 Wrap two half lapped layers of vinyl tape over the ground connector Figure ...

Страница 12: ...ar off last 1 2 25 50 mm of mastic Figure 23 If grounding was applied apply tape over mastic strips 2 rubber mastic 2 rubber mastic Figure 22 Stretch and tear off last 1 2 25 50 mm of rubber mastic Figure 23 7 2 Install the larger rejacketing tube by slowly pulling and unwinding the core counterclockwise The tube may need a slight push to keep it from folding back on itself Figure 24 Unwind Counte...

Страница 13: ... from folding back on itself Figure 25 Unwind Counter clockwise Figure 25 7 4 Connect optional grounding Note In applications where the splice is regularly exposed to high levels of ultra violet radiation i e direct sunlight wrap two half lapped layers of Scotch Super 33 Vinyl Electrical Tape or Scotch Vinyl Electrical Tape Super 88 over the re jacketing tubes ...

Страница 14: ... 4 R 4 3 A 3 T R 4 3 U 4 n w o r B 4 H 7 8 3 u C l A 0 0 5 I 0 C 0 5 3 T R A 4 3 U 3 H 6 0 1 3 u C l A 6 1 0 0 0 2 0 6 4 T R A 6 3 U 1 3 H 5 1 1 3 3 u C 9 1 0 0 0 1 5 7 3 T R 9 3 U 3 H 6 0 1 u C l A 9 1 0 0 0 2 5 7 4 T R A 9 3 U 5 H 5 2 1 3 3 u C 9 1 0 1 0 1 5 7 5 T R 9 3 U 4 H 6 0 1 u C l A 0 5 7 I 0 C 5 7 3 T R A 9 3 S 3 H 0 4 1 3 u C 4 2 0 0 0 1 0 0 1 4 T R 4 4 P T R 4 4 S 3 H 5 2 1 u C l A 4 2...

Страница 15: ...78 8127 8872 3 B 15 ...

Страница 16: ...on in writing by an authorized officer of 3M Warranty Limited Remedy Limited Liability This product will be free from defects in material and manufacture for a period of one 1 year from the time of purchase 3M MAKES NO OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE If this product is defective within the warranty period sta...

Отзывы: