4.2 If using cold shrink adapter tube:
Position adapter tube over the connector. Shrink adapter near center of
connector by pulling and unwinding the loose core end in a counter-clockwise direction
(Figure 13).
Cold shrink adapter tube
Figure 13
4.3 Clean cables using standard practice:
a. Do not allow solvent or abrasive to contact the cable semi-conductive insulation shield.
b. Do not reduce cable insulation diameter below 1.24" (31,5 mm) specified for the splice.
c. The insulation surface must be round, smooth and free of cuts/voids. Sanding may be necessary, finish
sanding should be done with a 300 grit or higher electrical grade abrasive.
d. Make certain that the cable insulation is smooth, clean and dry before continuing.
4.4 Apply red compound on cable insulations, making certain to fill in edge of cable semi-con.
Do not use
silicone grease
(Figure 14).
Apply Red
Compound
Apply Red
Compound
Fill semi-con step
Fill semi-con step
Figure 14
Содержание 5458A-IJ