2.0 Prepare Cables
2.1 Check to be sure the cable fits within the kit ranges as shown on the cover page.
2.2 Prepare cables according to standard procedures. Refer to template provided or illustration below for proper
dimensions
(Figure 1).
“A”
“B”
3 1/2"
(89 mm)
Insulation
Semi-Con
Neutral Wires
Cable Jacket
Typical Conductor Size*
kcmil (mm
2
)
Insulation OD Range
Inches (mm)
Jacket Cutback "A"
Inches (mm)
Semi-con Cutback "B"
Inches (mm)
500**-750
(240-400)
1.24–1.70
(31,5–43,2)
15 3/4
(400)
9 1/4
(235)
1000**
(500)
1.59–2.07
(40,4–52,6)
15 1/4
(387 mm)
8 3/4
(222)
*For 100% and 133% insulation levels, Insulation OD is the final determining factor.
**Cables must be within the Insulation OD Range of the splice kit and the connector must meet the dimensional requirements shown on the front page.
Figure 1
2.3 Carefully bend the cut neutral wires up and away from the cable semi-con as shown. Fold one Scotch® Mastic
Sealing Strip 2230 in half lengthwise and apply one wrap only at cable jacket edge under the neutral wires
(Figure 2).
Insulation
Semi-Con
Neutral Wires
Scotch® Mastic Sealing Strip 2230
Fold mastic strip in half lengthwise
Figure 2