3.4 For 500 kcmil copper connectors, or connectors with an O.D. between 1.05–1.24" (26,7–31,5 mm):
Park cold shrink adapter tube on cable insulation
(Figure 10).
Cold shrink adapter tube
Figure 10
3.5 Install connector. See table (on cover) for proper connector dimensions. (For standard 3M
™
Connectors, refer
to table at the end of this instruction for crimping information). Remove any excess oxidation inhibitor from
connector ends if aluminum connector is used
(Figure 11).
Connector
Figure 11
4.0 Install Splice
4.1 Apply a tape marker to semi-con insulation shield on cable which does not contain splice. Measure 11-1/2"
(292 mm) from center of connector
(Figure 12).
Tape Marker
Semi-con
11 1/2"
(292 mm)
Figure 12