14
MENU 6 – Setting insensitivity in three-position regulation
–
Shortly press P to select value 1 – 10 %
(1 – 10x blinking of LED2)
and keep pressing push-button P to store the
parameter to memory.
MENU 7 – Response in case of losing control signal in three-position regulation
– Shortly press P to select value OPEN
- 1x blinking of LED2,
or CLOSE
- 2x blinking of LED2,
or STOP
- 3x blinking of LED2,
and keep pressing push-button P to store the parameter to memory.
MENU 8 – Way of switching off in end-limit positions in 3P regulation
– Shortly press P to select value TORQUE
- 1x blinking of LED2,
or PO
- 2x blinking of LED2,
or PZ
- 3x blinking of LED2,
PO + PZ
- 4x blinking of LED2,
And keep pressing push-button P to store the parameter to memory.
PROCEDURE OF SETTING PARAMETERS BY PROGRAM DMS2
–
Before starting the actuator, it is necessary to set some parameters of the system by means of program
DMS2 on PC.
–
For safety reasons, the system is delivered in the state of induced error of Calibration when the functions are limited
in order to reduce the risk of damaging the actuator by wrong wiring. In controlling the actuator from program DMS2,
its run is stopped when any torque is induced.
Working torque
– Check and, if necessary, set the value of working torque 50 – 100 % in program DMS2.
Record of positions OPEN, CLOSED and AUTOCALIBRATION
The actuator should be adjusted so that the recorded position would stop the actuator before it is switched
off by torque. The actuator is shifted manually or electrically. The actuator in version CONTROL can be started
from menu MOTOR in program DMS2. In this case, the actuator does not respond to the set position and is
switched off by torque. In controlling from menu MOTOR, no torque may be induced. The torque should be left
manually.
Main window of setting program
Selection of electronics