PREMIER EX PLUS – OPERATION & INSTALLATION MANUAL
PAGE 17
DOCUMENT: GLT-MAN.115
ISSUE: 1 DATE: 22/8/05
AUTHOR: NRPJ
CONNECTIONS
+
+
+
+
+
+
+
+
+
+
+
+
NO CM NC NO CM NC
NO CM NC
+
AC AC
2 3 4 5 6
10
7
8
9
11
1
13 14 15
20
19
18
17
16
Conn Label
Function
1
HOLD/ABORT
TO CONNECT AN ABORT SWITCH TO STOP THE
BOTTLE OUTPUT
2
AUTO / MAN
TO CONNECT A REMOTE SWITCH TO TOGGLE
BETWEEN AUTO & MANUAL MODES
3
GAS FIRED
TO CONNECT THE BOTTLE OUTPUT SWITCH TO
CONFIRM THAT THE GAS HAS BEEN FIRED
4 MANUAL
RELEASE
TO CONNECT A MANUAL RELEASE CALL POINT.
WHEN THIS IS ACTIVATED IT STARTS THE SECOND
STAGE SOUNDERS & STARTS THE BOTTLE TIMER.
5
ZONE 1
DETECTION ZONE 1
6
ZONE 2
DETECTION ZONE 2
7
ADDR LOOP IN
TO CONNECT TO AN ADDRESSABLE PANEL FOR
CENTRAL MONITORING.
8
ADDR LOOP OUT TO CONNECT TO AN ADDRESSABLE PANEL FOR
CENTRAL MONITORING.
9 FIRST
STAGE
RELAY
VOLT FREE CONTACT. ACTIVATES ON FIRST STAGE
ALARM
10 SECOND
STAGE
RELAY
VOLT FREE CONTACT. ACTIVATES ON SECOND
STAGE ALARM
11
SND 1
FIRST STAGE ALARM OUTPUT
12
SND 2
SECOND STAGE ALARM OUTPUT
13
BOTTLE
BOTTLE OUTPUT TO SOLENOID VALVE
14
AUX 28V
AUXILIARY 28 V
15
FAULT RELAY
NORMALLY ENERGISED FAULT RELAY -VOLT FREE
16 XFO
SECONDARY
30V AC FROM TRANSFORMER SECONDARY
17
BATTERY
TO CONNECT 2 X 12V SLA BATTERIES
18
ISP PORT
TO PROGRAM THE MICROPROCESSOR
19 DIAGNOSTIC
PORT
FOR USE DURING PCB TESTING
20 DISPLAY
CONNECTOR
14 WAY RIBBON CONNECTOR TO DISPLAY PCB