PREMIER EX PLUS – OPERATION & INSTALLATION MANUAL
PAGE 9
DOCUMENT: GLT-MAN.115
ISSUE: 1 DATE: 22/8/05
AUTHOR: NRPJ
SET UP
BOTTLE OUTPUT TIMER DELAY.
This panel may be shipped with the timer setting in the “fault condition”. This is to force
the user to select a timer delay, rather than relying on a default setting.
TIME DELAY
SWITCH 5
SWITCH 6
SWITCH 7
SWITCH 8
FAULT
CONDITION
OFF OFF OFF OFF
30
SECONDS OFF OFF OFF ON
45 SECONDS
OFF
OFF
ON
OFF
1 MINUTE
OFF
OFF
ON
ON
1 MIN 15 SECONDS
OFF
ON
OFF
OFF
1 MIN 30 SECONDS
OFF
ON
OFF
ON
1 MIN 45 SECONDS
OFF
ON
ON
OFF
2 MINUTE
OFF
ON
ON
ON
2 MIN 15 SECONDS
ON
OFF OFF OFF
2 MIN 30 SECONDS
ON
OFF OFF ON
2 MIN 45 SECONDS
ON
OFF ON OFF
3 MINUTE
ON
OFF ON ON
3 MIN 15 SECONDS
ON
ON OFF OFF
3 MIN 30 SECONDS
ON
ON OFF ON
3 MIN 45 SECONDS
ON
ON ON OFF
4
MINUTE ON ON ON ON
LOOP ADDRESS SETTING
When connecting the EX Plus to an addressable loop, the panel address must be set.
The default setting is address 1 (all switches off). If you require a different address, then
select an address by setting the switches as shown below. (Note that on a loop, only 1
device can be set to a given address. 2 devices with the same address will cause a
double address fault)
ADDRESS SWITCH
1
SWITCH 2
SWITCH 3
SWITCH 4
1
OFF OFF OFF OFF
2
OFF OFF OFF ON
3 OFF
OFF
ON
OFF
4 OFF
OFF
ON
ON
5 OFF
ON
OFF
OFF
6 OFF
ON
OFF
ON
7 OFF
ON
ON
OFF
8 OFF
ON
ON
ON
9 ON
OFF OFF OFF
10 ON
OFF OFF ON
11 ON
OFF ON OFF
12 ON
OFF ON ON
13 ON
ON OFF OFF
14 ON
ON OFF ON
15 ON
ON ON OFF
16
ON ON ON ON