PREMIER EX PLUS – OPERATION & INSTALLATION MANUAL
PAGE 14
DOCUMENT: GLT-MAN.115
ISSUE: 1 DATE: 22/8/05
AUTHOR: NRPJ
ELECTRICAL SPECIFICATIONS
Mains Voltage
230 Vac. 59/60Hz +15%, -10%.
Charger Voltage
25 – 30 Vdc (set internally to 27.6V)
Battery Voltage
24V SLA (2 x 12V)
Battery Space
7.0 AH maximum
Mains Supply Protection
3.15 AF HRC 20 x5mm fuse
Charger Voltage Protection
1.6 AT 20 x 5mm glass fuse
Battery Supply Protection
3.15 AT 20 x 5mm glass fuse
Reverse battery protection
Battery fuse
Sounder Output (1
st
and 2
nd
stage)
24 Vdc nominal
Sounder Output protection
400mAF 20 x 5 mm glass fuse
Sounder EOL
10K
Max sounder circuit resistance
25 R
Auxiliary Supply Output
24 Vdc nominal
Auxiliary Supply protection
1 AT 20 x 5 mm glass fuse
Auxiliary Relay contacts (1
st
and 2
nd
stage)
30Vac / dc 1.0 A each
Bottle Output
24 Vdc nominal
Bottle Output protection
1.0AT 20 x 5 mm glass fuse
Bottle end of line
10K
Zone Voltage
20 Vdc nominal
Quiescent Zone current
8 mA per circuit
Zone end of line
2K7
Max Zone circuit resistance
100 R
Max resistance other circuits
100 R
Quiescent battery current (tone muted)
72 mA nominal
Quiescent bat current (tone not muted)
85 mA nominal
Max total load current (Snd 1 & 2 , Bottle)
1.6 A ( although each may be to fuse rating )
Circuits monitored for O/C and S/C
Bottle output,
1
st
and 2
nd
stage snd outputs,
Zones 1 and 2.
Circuits monitored for O/C only
Hold/Abort
Auto/Manual,
Gas fired,
Manual release.
(S/C gives active condition although a resistance of up to
500 R will still give an active condition)
FUSE RATINGS
Mains Fuse
3.15 A HBC
Charger Fuse
1.6A T
Battery Fuse
3.15A T
First Stage Sounder Fuse
400 mA F
Second Stage Sounder Fuse
400 mA F
Bottle Fuse
1A T
Aux 28V Fuse
1A T