background image

© Copyright 2021 Zoeller

®

 Co. All rights reserved.

7

TROUBLESHOOTING INFORMATION

1. 

DC Pump won’t run.

 

(a)  Check for proper connections.

 

(b)  Check all wire terminal points. Clean if required.

 

(c)  Check for low battery. Service battery if required.

 

(

d

)  Check 

30 amp fuse on controller. If fuse is blown, replace with 30 amp 

automotive blade fuse.

 

(

e

Remove pump. Check for obstruction in pump preventing impeller from 

rotating.

 

(f)  Float switch was not “on” for more than 1 second. A quick up/down of 

a switch will not turn the pump on because the controller is designed 

with “splash activation protection”.

 

(g)  During a float fault, the operational float is disregarded until the controller 

is reset.

2. 

Pump runs but moves very little or no water.

 

(a)   Check for low battery. Battery will recharge if green System Ready 

LED indicates power has been restored and the float switch is in the 

off position.

 

(b)  If immediate usage is required, remove and replace dead battery with 

a fully recharged battery.

 

(c)  Under certain conditions the pump may continue to run on a low battery 

without sufficient power to remove water. Pump will stop running once 

battery is below minimum voltage threshold.

 

(d) 

CAUTION

 Weak batteries can be recharged but may not store 

sufficient energy for full service. A weak, recharged battery can only 

be detected by reduced pumping time or by professional load testing 

equipment. The battery should be checked by a qualified battery dealer.

 

(e)   Verify pump is connected completely.

 

(f)  Check to make sure pump weep hole is clear and unit is not airlocked.

 

(g)   Make sure discharge piping is not blocked.

3. 

Pump cycles too frequently.

 

(a)  Check positions of rubber stops on the operational float rod and adjust 

if necessary.

4. 

Pump runs, but pumps water intermittently.

 

(a)  Pump may be air locking. Check flow of water incoming to sump. If water 

is entering the sump at a high velocity creating a turbulent condition, a 

mixture of air and water may cause a complete or partial air lock and 

reduce or stop the flow of water in the discharge pipe.

 

(b)  Baffle the incoming stream of water to reduce turbulence. Diverting 

water stream against wall of basin usually corrects an air lock problem.

5.  Water level stays high. DC Pump continues to run.

 

  (a)  Battery is low or pump may have blockage in screen, impeller, or piping 

system.

 

  (b)  If  power  has  been  restored  and  water  in  sump  remains  high  check 

primary pump. Service if required.

6.  Alarm sounds during battery recharge cycle.

 

  (a)  To silence alarm if alarm will not reset, unplug the charger from 115 V 

wall outlet, then disconnect the black lead from charger on negative (-) 

battery post. Check battery. Replace if necessary. Reconnect and refer 

to Installation Instructions.

To perform a Factory Reset, hold the Silence and Test buttons together. A Factory Reset restores all settings to their original setting. Be sure all switches, 

pump, battery and AC connections are good before the Factory Reset. 

 

 

ELECTRICAL PRECAUTIONS- 

Before servicing a pump, always shut off the main power breaker and then unplug the pump - making 

sure you are wearing insulated protective sole shoes and not standing in water.  Under flooded conditions, contact your local electric company or 
a qualified licensed electrician for disconnecting electrical service prior to pump removal.

 Submersible pumps contain oils which becomes pressurized and hot under operating conditions. 

Allow 2-1/2 hours after disconnecting before 

attempting service.

If the above checklist does not uncover the problem, consult the factory - Do not attempt to service or otherwise disassemble pump. 

SERVICE CHECKLIST- PRIMARY PUMP

CONDITION

COMMON CAUSES

A.

Pump will not start or run.

Check fuse, low voltage, overload open, open or incorrect wiring, open switch, impeller or seal bound mechanically, motor or 

wiring shorted. Float assembly held down. Switch damaged or out of adjustment.

B. Motor overheats and trips 

overload or blows fuse.

Incorrect voltage, negative head (discharge open lower than normal) impeller or seal bound mechanically, motor shorted.

C. Pump starts and stops too often.

Float switch tether length too short, check valve stuck open, or none installed in long distance line, overload open, bidding, 

sump pit too small.

D. Pump will not shut off.

Debris under float assembly, float bound by basin sides or other, switch, damaged or out of adjustment.

E. Pump operates but delivers little 

or no water.

Check inlet, strainer housing, discharge pipe, and vent holes for obstructions.  Discharge head exceeds pump capacity. Low 

or incorrect voltage. Incoming water containing air or causing air to enter pumping chamber.  

F. Drop in head and/or capacity after 

a period of use.

Increased pipe friction, clogged line or check valve. Abrasive material and adverse chemicals could possibly deteriorate impeller 

and pump housing. Check discharge line. Remove base and inspect.

G. If tank or fittings leak.

Carefully tighten pipe joints (use pipe dope) and screws. Check gasket location, tighten lid evenly. Do not over tighten fittings 

or screws.

Summary of Contents for ProPak AQUANOT KEY 507/73

Page 1: ...backuppumpsrequirestheuseofavariable level float switch for operation It is the responsibility of the installing party to ensure that the float switch will not hang up on the pump apparatus or pit peculiarities and is secured so the pump will turn on and off It is recommended that the pit be 18 45 7 cm in diameter or larger to accommodate both a primary and a DC backup pump 6 For indoor use only C...

Page 2: ... This warranty gives you specific legal rights and you may also have other rights which vary from state to state In instances where property damages are incurred as a result of an alleged product failure the property owner must retain possession of the product for investigation purpose 1 Electrical wiring and protection must be in accordance with National Electrical Code and any other applicable s...

Page 3: ... Battery Box Construction Non corrodible plastic Safety Snap tight lid keeps battery safe and clean When AC power is available the controller will replace the power used by the pump once the pump shuts off The DC controller is equipped with a 10 amp charger for maintaining the battery in a ready state and recharging the battery after use when AC power is restored Time for recharge depends upon the...

Page 4: ...h After 1 second splash activation prevention delay the DC backup pump will run and the alarm will sound after 1 more second Lower the operational float switch after the alarm sounds Take care that the intake of the DC pump is set above the intake of the primary pump If water was pumped the Yellow DC Pump LED and alarm will remain on indicating that the pump ran and pumped water The alarm can be s...

Page 5: ...d 5 OUTLET PRIMARY PUMP 1 MIN IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP FIG 1 DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX AQUANOT KEY CONTROLLER OUTLET CONTROLLER TYPICAL INSTALLATION FIGURE 1 SK3260 ...

Page 6: ...11 Hardware pak charger switch mode 1 152864 12 Power supply 1 157388 AQUANOT KEY FLOAT SWITCH SK3186 LOCKING PIN MUST BE INSTALLED UNDER FLOAT ROD INTHIS LOCATION MOLEX 2 PIN CONNECTOR MOLEX 4 PIN CONNECTOR SK3262 OPERATIONAL FLOAT DC PUMP LED TEST BUTTON BLACK LEAD NEGATIVE FLOAT STATUS LED SILENCE BUTTON WHITE LEAD POSITIVE AC POWER ADAPTER PORT 30 AMP FUSE DC PUMP SYSTEM READY LED BATTERY LED ...

Page 7: ...f required 6 Alarm sounds during battery recharge cycle a To silence alarm if alarm will not reset unplug the charger from 115 V wall outlet then disconnect the black lead from charger on negative battery post Check battery Replace if necessary Reconnect and refer to Installation Instructions To perform a Factory Reset hold the Silence and Test buttons together A Factory Reset restores all setting...

Page 8: ...ord label also describes LED and button functionality CARBON MONOXIDE DETECTORS Some battery types used in battery backup systems regardless of brand or manufacturer have the potential to give off gaseous by products when charging Some of these by products can produce a rotten egg odor Also some of these by products can cause a CO detector to falsely activate In order to help prevent false activat...

Reviews: