background image

© Copyright 2021 Zoeller

®

 Co. All rights reserved.

4

INSTALLATION

 5. Connect the leads from the control charger to the battery terminals.  White 

positive (+) lead to positive terminal and black negative (-) lead to negative 

battery terminal.  Upon proper connection, test alarm will sound.  Press 

alarm reset to silence.  This indicates proper charger to battery connection.  

CAUTION

 Correct battery hook up is essential for operation of the 

system.  Use nuts supplied with battery and eyelet connectors on battery 

wire leads.  On batteries with different sized posts, the positive terminal

   is  the  larger  post,  3/8”  (10mm)  diameter.  The  smaller  post,  5/16”  (8mm) 

diameter  is  the  negative  terminal.  This  will  be  indicated  on  the  battery.  
Apply grease to the terminals to help prevent corrosion.

 6. Connect the plugs for the pump, operational switch, and power supply into 

the appropriate receptacles on the controller.

  7.  Close battery box and secure cover.  

  8.  Plug the control power cord into the 115 V wall outlet.  The primary sump 

pump and the control charger should be on separate circuits.

  9.  Reconnect power to primary sump pump.

 1. 

The installation kit includes the necessary fittings and  parts needed to install 

as in Figure 1. A check valve is incorporated in the discharge of the backup 

pump.

  2.  Select  location  for  battery  and  control  charger.    Control  charger  must  be 

within 6' (1.8 m) of a 115 V wall outlet and within 6' (1.8 m) of pump and basin.  

Connect to a separate circuit, different than the primary pump.

  3.  Make certain the float switch clamp is tight on the pipe to avoid slippage.  

  

Ensure  that  the  “off”  level  of  the  float  is  1"  (25  mm)  minimum.  above  the 

discharge tee of 

the DC backup pump (see figure 1).  Position pumps in the 

sump and move float up and down, making sure of free movement without 

interference from any obstructions inside the sump or lid.  Very shallow sumps 

may require some adjustment to avoid overfilling or backing up of water into 
the sump inlet.  The float switch can be moved on the discharge pipe or the 
rubber stops can be adjusted as necessary.  Cut extra float rod length below 
lower float stop to prevent debris from interfering with float operation (see 
Figure 2).

  4.  Mount the Key controller to the wall.  If more convenient, the control charger 

may  be  set  on  a  nearby  shelf  or  ledge.  The  Key  controller  can  also  be 

mounted to the mounting posts on top of the battery box lid.  

INITIAL START-UP AND OPERATION

 

1.  Test the installation for leaks by running water into the sump, allowing 

for normal operation of the primary pump.

  2.  Check the controller. The System Ready light will be green when the unit 

is plugged into the 115 V wall outlet. The battery will indicate its condition 

when the controller has DC power. When the unit is first plugged in, all 

lights will flash and alarm will sound to verify all lights and the alarm work. 

The Key controller powers up expecting both switches to be connected. If 

one or both float switches are not connected, there will be various alarms 

depending on what is connected. If this occurs, simply plug in the switch 

and then reset the alarms by holding the Silence button for 3 seconds. 

Note that the charger may not begin charging for several minutes.

  3.  Disconnect the primary pump from its power source before touching 

any component in the sump pit.

  4.  Lift the Key

’s operational float switch. After 1 second “splash activation 

prevention” delay, the DC backup pump will run, and the alarm will 

sound after 1 more second. Lower the operational float switch after the 

alarm sounds. 

Take care that the intake of the DC pump is set above the 

intake of the primary pump. If water was pumped, the Yellow DC Pump 

LED and alarm will remain on, indicating that the pump ran and pumped 

water. The alarm can be silenced by pressing the Silence button. The 

yellow LED can be cleared by holding the Silence button for 3 seconds to 

reset. If the operational float is held on while there is no water to pump, 

the controller will turn the pump on and off a few times before running 

the pump continuously. This is to purge a suspected air lock. When the 

float is lowered, the pump will turn off, but the yellow DC Pump LED will 

not persist. The yellow DC Pump LED and alarm only stay on if the pump 

actually pumps water. The intention of this behavior is so the installer can 

turn the pump on and off for testing during installation without repeatedly 

having to reset the controller. If the operational float is removed/unplugged, 

there will be an alarm and a red flashing Float Status LED until silenced 

or remedied. 

  

CAUTION

Continuous dry running may cause overheating and damage 

the pump seals. Upon release of the float switch, the pump will shut off. 

Be certain there are no obstructions around the float or stem that will 

prevent the switch from turning off.

  6.  Complete the final testing of your installation by ensuring the primary 

pump is still disconnected from power. Then, unplug the Key controller 

from the 115 V wall outlet. Run water into the sump until the DC backup 

pump is activated by the operational float switch. Check all connections 

for leaks.

  7.  Press  the  Silence  button  when  the  pump  is  running.  This  will  silence 

the alarm. The pump will continue to run until the operational float is 

deactivated.

  8.  Reconnect the controller and the primary pump to the AC wall outlets. The 

primary pump may come on, lower the water level in the sump back to its 

normal operating level, and shut off. Both primary and backup systems 

are now ready for use. Hold silence button for 3 seconds to reset the Key 

controller.

  9.  The battery LED will be yellow during normal charging operation. See 

page 6 and 7 for a description of controller functions.

It is important to understand that the Key controller is an advanced technology product that has capabilities beyond those seen in other battery backup products. For 

those unfamiliar with the product, behaviors in the Key may initially seem unusual. For example, the controller is able to recognize potential air lock situations and 

remedy with an on/off/on/off/on routine proven to purge the problematic air from the pump.
 

The LEDs have specific patterns and behaviors that differ from other products on the market. For example, the DC Pump LED will stay Yellow after pumping water, 

alerting the homeowner of a DC pump-run event. If the pump runs and does NOT pump water (for example when lifting the float manually as a test with the pump 

above the waterline), the LED will not stay Yellow. This is meant to be an aid to the installer in order to test the pump without having to reset it each time.

When the float is disconnected, the alarm will sound and the Red Float Status LED will blink indicating that the float state has changed. Before leaving the installation 

site, the installer must initiate a Reset by holding the Silence button for 3 seconds. This will ensure that all systems are in a standby, ready state.

Summary of Contents for ProPak AQUANOT KEY 507/73

Page 1: ...backuppumpsrequirestheuseofavariable level float switch for operation It is the responsibility of the installing party to ensure that the float switch will not hang up on the pump apparatus or pit peculiarities and is secured so the pump will turn on and off It is recommended that the pit be 18 45 7 cm in diameter or larger to accommodate both a primary and a DC backup pump 6 For indoor use only C...

Page 2: ... This warranty gives you specific legal rights and you may also have other rights which vary from state to state In instances where property damages are incurred as a result of an alleged product failure the property owner must retain possession of the product for investigation purpose 1 Electrical wiring and protection must be in accordance with National Electrical Code and any other applicable s...

Page 3: ... Battery Box Construction Non corrodible plastic Safety Snap tight lid keeps battery safe and clean When AC power is available the controller will replace the power used by the pump once the pump shuts off The DC controller is equipped with a 10 amp charger for maintaining the battery in a ready state and recharging the battery after use when AC power is restored Time for recharge depends upon the...

Page 4: ...h After 1 second splash activation prevention delay the DC backup pump will run and the alarm will sound after 1 more second Lower the operational float switch after the alarm sounds Take care that the intake of the DC pump is set above the intake of the primary pump If water was pumped the Yellow DC Pump LED and alarm will remain on indicating that the pump ran and pumped water The alarm can be s...

Page 5: ...d 5 OUTLET PRIMARY PUMP 1 MIN IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP FIG 1 DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX AQUANOT KEY CONTROLLER OUTLET CONTROLLER TYPICAL INSTALLATION FIGURE 1 SK3260 ...

Page 6: ...11 Hardware pak charger switch mode 1 152864 12 Power supply 1 157388 AQUANOT KEY FLOAT SWITCH SK3186 LOCKING PIN MUST BE INSTALLED UNDER FLOAT ROD INTHIS LOCATION MOLEX 2 PIN CONNECTOR MOLEX 4 PIN CONNECTOR SK3262 OPERATIONAL FLOAT DC PUMP LED TEST BUTTON BLACK LEAD NEGATIVE FLOAT STATUS LED SILENCE BUTTON WHITE LEAD POSITIVE AC POWER ADAPTER PORT 30 AMP FUSE DC PUMP SYSTEM READY LED BATTERY LED ...

Page 7: ...f required 6 Alarm sounds during battery recharge cycle a To silence alarm if alarm will not reset unplug the charger from 115 V wall outlet then disconnect the black lead from charger on negative battery post Check battery Replace if necessary Reconnect and refer to Installation Instructions To perform a Factory Reset hold the Silence and Test buttons together A Factory Reset restores all setting...

Page 8: ...ord label also describes LED and button functionality CARBON MONOXIDE DETECTORS Some battery types used in battery backup systems regardless of brand or manufacturer have the potential to give off gaseous by products when charging Some of these by products can produce a rotten egg odor Also some of these by products can cause a CO detector to falsely activate In order to help prevent false activat...

Reviews: