background image

11

© Copyright 2022. All rights reserved.

In order to prevent plugging in the Aeration Chamber, the 

backwash cycle activates at a preset schedule. If there is no 

backwash cycle or too short of a backwash cycle, the unit’s 

performance will be adversely affected. Likewise, if the backwash 

cycle is too long, performance will be compromised.

The backwash cycle begins at 2:00 AM and lasts for five minutes. 

One hour later, another five minute backwash cycle occurs. Even 

with these default settings, the waste water inflow could be too 

low or too high to optimize the performance and therefore, must 

be checked during each inspection.

The backwash cycle and sludge transfer from the Aeration 

chamber take place at the 

same time. Verify that the air flow is 

uniform across the Aeration chamber between the two sides 

during a backwash cycle. If not, adjust the red backwash valve 

(3) accordingly.

The recirculation flow is designed to be 1.2-1.8 times that of the 
average inflow. Table 4 indicates approximate flow rates for each 
unit.  However,  fine  adjustments  may  be  necessary  to  ensure 

optimum performance.

Setting the flow rate:
•  Adjust the flow using rates in Table 4.
•  The flow rate is adjusted by rotating the gray recirculation valve 

(2) and observing the flow at the pipe end.

•  There are prescribed lines at the outlet of the recirculation pipe 

to aid in approximating the correct flow.

Measuring the flow rate:
•  The actual flow rates must be measured to verify flow

  after adjustment of the valve and observation at the pipe end.

•  Measure the time in seconds required to fill a 1000 mL container.

•  Compare the time to value ranges in Table 4.
•  If necessary, adjust the valve again and collect another sample 

to verify the correct flow rates.

Setting the flow rate: 

•   Switch to a manual backwash cycle by pressing the pink 
"Manual  Backwash" button on the switching valve control pad.
•  

Set  the  backwash  flow  rate  by  adjusting  the  gray  sludge 

transfer   valve (4). Use Table 5 to determine the typical setting for 
each Fusion

®

 model.

Measuring the flow rate:

•  

Measure the actual backwash flow rate at the outlet of the sludge 

return  pipe  in  the  first  chamber  the  same  way  the  recirculation 
flow rate is measured.

 
•   Adjust the gray sludge transfer valve (4) if necessary to obtain 

the proper flow

•   Return the switching valve to normal aeration mode by pressing 
the pink button on the switching valve's control pad.

It  is  important  not  to  set  the  flow  rate 

too high because it can cause excessive 

agitation  within  the  first  chamber  (Sedimentation 

Chamber). This could result in poor performance.

RECIRCULATION FLOW ADJUSTMENT

BACKWASH FLOW ADJUSTMENT

Reset (factory default settings):

1.  Press Reset.
 

Clock is set to 0.00 (midnight).

 

Backwash Time is set to 2:00 AM.

 

Backwash Frequency is set to 2 per  

 

 

 

 

day.  Backwash Duration is set to 5 mins.

To Adjust Clock & Backwash Settings:

1.  Press Mode SW.  Note the blinking arrow indicating 
(hr.) under "Clock"  at the right of the screen.
2.  Press Set SW to select the current hour of the day. 
3.  Press Mode SW.  Note the blinking arrow indicating 
(min.) under "Clock" at the right of the screen.
4.  Press Set SW to select the current minute of the hour.
5.  Press Mode SW.  Note the blinking arrow indicating  
Time (hr.) under "AUTO Back Wash" at the left of the 
screen.
6.  Press Set SW to select the hour that the system will 
begin to back wash. (A setting of 2 is standard)
7.  Press Mode SW.  Note the blinking arrow indicating 
Freq./Day under "AUTO Back Wash" at the left of the 
screen.
8.  Press Set SW to select either 1 or 2 back wash cycles 
that the system will perform per day.  A setting of 2 is 
standard.
9.  Press Mode SW.  Note the blinking arrow indicating 
Duration (min) under "AUTO Back Wash" at the left of the 
screen.
10.  Press Set SW to select either 5 or 10 minute duration 
for back wash cycle.  A 5-minute cycle is standard.
NOTE:  A 24-hour clock is used in place of AM/PM 
designations.

 

Figure 15

TIMER SWITCHING VALVE

Summary of Contents for Fusion Series

Page 1: ... years from date of purchase by the end user No allowance will be made for shipping charges damages labor or other charges that may occur due to product failure repair or replacement This warranty does not apply to and there shall be no warranty for any material or product that has been disassembled without prior approval of Manufacturer subjected to misuse misapplication neglect alteration accide...

Page 2: ...rom the liquid In the second chamber plastic media with large surface areas are used to increase contact between water and beneficial bacteria to optimize treatment A small linear air blower is used to move air oxygen into the third chamber for the aerobic process The final effluent leaving the system will have been treated to secondary quality effluent HOW A FUSION SERIES TREATMENT SYSTEM WORKS F...

Page 3: ...ous nitrogen The gaseous nitrogen then escapes to the atmosphere 3 Aeration Chamber The aeration chamber consists of an aerated upper section and a filter media lower section The chamber is filled with hollow cylindrical filter media 0 6 inch diameter 15 mm and 0 55 inches long 14 mm Biological treatment takes place on the filter media surface Aeration is continuous Residual suspended solids are c...

Page 4: ...repair them immediately Excessive water use may hydraulically overload your Fusion system and reduce its treatment efficiency Excessive water use may also overload your soil absorption field and cause failure HIGH USE WATER DEVICES The draining of hot tubs and swimming pools into your Fusion system could cause hydraulic overloading and may reduce the treatment efficiency Please drain these devices...

Page 5: ... reconnect power to either the blower or alarm panel once it has been submerged Immediately contact your authorized Fusion maintenance provider to inspect the Fusion the blower and the alarm panel Your maintenance provider will repair or replace the components as needed Fusion Series systems are compact efficient and designed to be installed in a typical residential light commercial environment Th...

Page 6: ...amp soil around perimeter of the unit as it is backfilled to stabilize the unit and to reduce settling 7 Finalize backfill with a mounded contour so that surface water is shed away from the unit Under no circumstances should surface water be allowed to accumulate around unit 8 CAUTION MAXIMUM soil burial depth over the unit is 36 inches 914 mm EXCAVATION AND INSTALLATION BACKFILLING COLD WEATHER I...

Page 7: ...er by 6 inches in height Do not install more than two riser heights together for a maximum of 12 inches burial depth Prepare risers by applying two complete circular beads of silicone or other like sealant around riser flange in order to seal risers and make the installation watertight Install the 24 inch diameter riser onto the already installed riser adapters with the provided stainless steel sc...

Page 8: ...on lines 8 Attach the small diameter black air tubing included in the blower box to barbed fitting on PVC tee Black air tubing and blower cord should be routed to the control panel through conduit Attach the black air tubing line to the air pressure sensor barbed fittings in the panel Figure 10 If air tubing is not connected to backwash and recirculation lines the panel will alarm 9 Connect the re...

Page 9: ...ncrete Volume W H Concrete Volume W H Concrete Volume W H Concrete Volume FT FT FT3 CY FT FT FT3 CY FT FT FT3 CY FT FT FT3 CY ZFL 2800 2 8 3 0 432 16 2 7 2 8 370 14 2 6 2 5 323 12 2 3 2 10 334 13 ZFL 4000 3 0 3 0 531 20 3 0 2 6 443 16 2 10 2 5 400 15 2 6 2 11 416 16 Model 24 Cover 30 Cover 36 Cover W H Concrete Volume W H Concrete Volume W H Concrete Volume FT FT FT3 CY FT FT FT3 CY FT FT FT3 CY Z...

Page 10: ...electrical codes 2 The blower should be directly wired into the alarm panel The alarm panel must be located in a dry location that is accessible for maintenance Please see the wiring diagram and instructions enclosed with the alarm panel 3 Make certain the timer within the control panel is set to the proper time The timer unit display should be set to 10 hours and the timer dial needle set to 3 6 ...

Page 11: ...ng valve control pad Set the backwash flow rate by adjusting the gray sludge transfer valve 4 Use Table 5 to determine the typical setting for each Fusion model Measuring the flow rate Measure the actual backwash flow rate at the outlet of the sludge return pipe in the first chamber the same way the recirculation flow rate is measured Adjust the gray sludge transfer valve 4 if necessary to obtain ...

Page 12: ...es 1 Transparency Measures the ability of the water to transmit light Using the ladle fill the transparency tube with a water sample collected from the clean water storage chamber Looking down through the water column slowly drain the transparency tube using the valve on the flexible hose until you can first distinguish between the black and white colors on the secchi disk in the bottom of the tub...

Page 13: ...olor remnants of digestion are often yellowish in color White sometimes present after new construction often due to drywall mud PART B Anaerobic Chamber collect samples from the outlet baffle of the anaerobic chamber to be used for the following analyses 1 Transparency A transparency reading more than 20 cm is preferred 2 Scum Should not be present unless recirculation and orbackwashrateistoohigho...

Page 14: ...aeration line after the switching valve as shown in Fig 20 Gradually open the water faucet and introduce water into the system Rotate valve 1 back and forth from the 0 to the 100 position several times to flush Turn off the water remove the water line and reconnect the airline to the blower Set valves 1 and 2 back to the appropriate positions See Recirculation Flow Adjustment pg 10 C Cleaning the ...

Page 15: ...ING 1 Odor Offensive odors are often the result of insufficient or inappropriate bacterial growth Causes may include a young or unestablished system insufficient air introduction or the addition of detrimental chemicals or poisons into the system Ensure the blower and air delivery systems are functioning Check with the homeowner regarding chemical use and disinfection habits Check all risers and l...

Page 16: ...MAINTENANCE PUMPING AS NEEDED Figure 21 Pump out procedures Step 1 Remove the scum Step 2 Remove the sludge 1 2 Sedimentation separation tank Vacuum Step 1 Remove the scum Step 2 Remove the sludge on the filter media Step 3 Remove the sludge under the media while washing the filter with tap water 1 Anaerobic filter tank Vacuum Tap water 2 3 ATTENTION Remove the scum first If you remove the sludge ...

Page 17: ...17 Copyright 2022 All rights reserved ...

Page 18: ... and pull the rubber elbow away from the discharge port of the diaphragm housing Carefully use a small flat bladed screw driver to unbond uncouple the rubber tube from the discharge port then pull it away See Figure 29 6 Next pull the diaphragm housing away See Figure 30 7 Unscrew the hex nut at the center of the diaphragm and proceed to pull the diaphragm from the magnetic bar See Figure 31 8 If ...

Page 19: ... 94 100 Weight in Pounds 2425 3748 Lids and Access 24 Diameter 4 4 Blower Information Alita AL 250 1 Alita AL 300 1 Switching Valve P N 151438 1 1 Air Line Size s 3 4 Recirculation 1 1 1 Backwash 1 1 Inlet Outlet Information Influent Invert inches 21 21 Effluent Invert inches 28 28 Inlet Outlet Pipe Size Inches 4 4 Blower Details Voltage Amps Sound dB Air Flow L min Weight Alita AL 250 120 3 7 46 ...

Page 20: ...ight 2022 All rights reserved MAIL TO P O BOX 16347 Louisville KY 40256 0347 SHIP TO 3649 Cane Run Road Louisville KY 40211 1961 502 778 2731 1 800 928 PUMP FAX 502 774 3624 Visit our website zoellerpumps com ...

Reviews: