15
Led lit continuously Meaning
“défaut thermique
ventilateur”
= fan heat fault
Not used on Sirocco
“défaut pressostat
HP ou BP”
= high or low
pressure switch fault
triggering HP and/or LP switch and/or phase order relay KA4 (only on
Sirocco three-phase)
- HP : check that the ventilator is operational, that the air filter is clean and
the belt is tight enough,
- LP: insufficient gas, call a specialist,
- KA4: check for the presence of the 3 phases, if so, see §1.4.2.
“défaut thermique
compresseur”
= compressor heat
fault
Not used on Sirocco
“déclenchement
alarme”
= Triggering of the
alarm
- HP and/or LP switch triggered more than 3 times in one hour
- order phase relay KA4 triggered (only on Sirocco three-phase)
“défaut hors
température”
= temperature range
fault
-
temperature < than 10°C or > than 40°C (compressor stopped),
-
restart sensor is out of order.
-
In all cases, if the ventilator is active before the triggering of this fault, it is
maintained for 3 minutes before stopping.
-
If the returns to within its operating range:
-
there is a 30 seconds delay before the fault is cleared,
-
there is a 3 minute delay before restarting the compressor and the fan (if a
dehumidification request is still active)
“cycle de dégivrage”
= defrosting cycle
-
cooling circuit temperature < than -5°C or > than 40°C,
-
a defrosting cycle is in progress (temperature is >-5°C). The compressor is
stopped and ventilation is maintained,
-
the defrosting sensor is out of order.
The defrosting cycle stops when the temperature of the sensor goes over
2.2°C. If the sensor is out of range (<-5°C or >40°C) during the active
defrosting cycle, this LED remains on for 3 minutes with the ventilation
operating, before it stops.
In all cases, if the ventilator is active before the triggering of this fault,
ventilation is maintained for 3 minutes before stopping.
If the sensor returns within its operating range:
-
there is a delay of 30 seconds before the fault is cleared,
-
there is a 3 minute delay before the compressor and fan restart (if a
dehumidification request is still active)
Others
Description
“VI/VP switch”
“intermittent ventilation” (standard setting)
or “permanent ventilation” (to permanently circulate the pool hall air)
Using VI, a post-ventilation is active for 3 minutes.
The ventilation is active when:
- dehumidification is triggered,
- a defrosting cycle is started,
- pool hall air heating is triggered,
-
active for at least 5 minutes in one hour without any of these
triggers.
On VP, the compressor starts after a delay of 3 minutes.
“Connecteur module
de prog.”
= programming
module connector
ECP 600 programming connector or implementation of a diagnosis module
by the technical support department
ECP 600 250Vac T=10A 6,3x32 fuse
Summary of Contents for SIROCCO 110
Page 21: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 22: ...1 Electric diagram Sirocco 55 80 110 single phase...
Page 23: ...2 Sirocco 110 three phase...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...