8
1.3.6 Connection of the condensation drainage
Plan for an adequate slope to ensure a good flow. Drainage shall be via a siphon or a funnel
(condensation drainage pipe Ø12/18). Outlet provided for at the left of the appliance (condition ex-
works), with possibility of moving it to the right.
Make sure the siphon is filled with water in such a way as not to create air suction by the condensation
drainage pipe.
For placing the condensation drainage: see mark “A Ø12/18” § “dimensions” in the appendix.
1.3.7 Electric connections
1.3.7.1 Access to the electric box
1.3.7.2 Voltage and protection
The electrical supply must be provided through a protection and circuit breaking device (not
supplied) complying with the standards and regulations in force in the country where it is installed (in
France standard NF C 15100).
Electrical protection: 30 mA ground fault circuit breaker (at the head of the line).
1.3.7.3 Cable sizes
Supply cable size: for cables of a maximum length of 20 metres (calculation basis: 5A/mm²), this
must be checked and adapted depending on installation conditions.
Option
Voltage
Nominal
power
consumption
Maximum
power
consumption
Cable size
Unit
A
A
mm²
Sirocco 55
single-phase
without option or
hot water battery
230V-50Hz-
4.45
5.9
3 x 2.5
3G2.5
Extra heating 2
kW
230V-50Hz-
13.2
14.6
3 x 4
3G4
Sirocco 80
single-phase
without option or
hot water battery
230V-50Hz-
5.05
8
3 x 2.5
3G2.5
Extra heating 3
kW
230V-50Hz-
18
21
3 x 6
3G6
Sirocco 110
single-phase
without option or
hot water battery
230V-50Hz-
6.35
9.8
3 x 2.5
3G2.5
Extra heating 4.5
kW
230V-50Hz-
26
29.4
3 x 10
3G10
Sirocco 110
three-phase
without option or
hot water battery
400V-50Hz-
2.8
3.8
5 x 2.5
5G2.5
Extra heating 4.5
kW
400V-50Hz-
9.3
10.3
5 x 2.5
5G2.5
Acceptable voltage variation tolerance: ± 10% (during operation),
Electric cables must be fixed.
Prior to any operation, check that the voltage on the identification plate of the
appliance corresponds to the mains voltage available on site.
2
On each side
1
3
EN
Summary of Contents for SIROCCO 110
Page 21: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 22: ...1 Electric diagram Sirocco 55 80 110 single phase...
Page 23: ...2 Sirocco 110 three phase...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...