connection to a ZPCE double circuit gas boiler: connect the terminals 3-6 of the terminal board, to
terminals 3-6 of the boiler terminal board,
adjust the thermostat between to 26 and 28°C (maximum 30°C), in general set the air temperature
1 to 2°C higher than the pool water temperature,
a post-ventilation runs for 3 minutes when the reference temperature is reduced on the thermostat
located in the pool hall (with the “VI/VP” switch on “VI”, without any dehumidification or defrosting
cycles in progress): check that the circulator stops.
2. Troubleshooting
2.1 Status and faults in the ECP 600 settings
Terminals
Description
N - R
mains-supply 230Vac-50Hz to the ECP600 regulator
20 - 21
output from compressor supply 230 Vac -50Hz
30 - 31
230Vac-50Hz output (not used) and protected by the ECP600 fuse
22 - 23
ventilator 230Vac-50Hz output
25 - 24
output for circulator hot water battery option 230Vac-50Hz
26 - 27
output alarm report 230Vac-50Hz
28 - 29
output contact “NO” (without polarity) control of heat source hot water battery option
11 – 12 - 13
Input control sensor type PTC (inlet or defrost)
4 - 5
power supply 12Vac-50Hz
7
input 6Vac-50Hz given by the hygrostat function (request active if 6Vac-50Hz
between 7 and 4)
2
input 6Vac-50Hz given by the thermostat function (request active if 6Vac-50Hz
between 2 and 4)
8
input 12Vac-50Hz fan heat fault (shunted not active) (fault active if 0Vac-50Hz
between 8 and 4, “défaut thermique ventilateur” led lit up)
9
input 12Vac-50Hz faults BP and/or HP, and/or phase order (Sirocco three-phase)
(fault active if 0Vac-50Hz between 9 and 4, “défaut pressostat HP ou BP” led lit up)
10
input 12Vac-50Hz compressor heat fault (shunted not active) (fault active if 0Vac-
50Hz between 10 and 4, “défaut thermique compresseur” led lit up)
Led lit continuously
Meaning
“compresseur”
= compressor
the compressor is operational (blinking = temporisation in process)
“EPROM”
ECP600 regulator out of order
Warning - low temperature: if the dehumidifier hot water battery is not supplied by a
boiler, but by an aero-thermal or a geothermal system, the heating circuit water will be at
a maximum temperature of 45-40°C. The power of the battery will then be considerably
lower (3 to 4 times less) than the nominal power given for water at 90-70°C. If the power
of the battery is lower than the heating needs of the room, plan for additional heating by
radiator, heated floor or fan convector.
If your pool has a cover (shutter or bubble sheet type, etc.), you can lower the room
temperature (by adjusting the thermostat to about 20°C) when it is in place and raise the
pool hall temperature before removing the cover.
Terminals 3-6 can also ensure a heat source control function (see §1.3.7.4)
EN
Summary of Contents for SIROCCO 110
Page 21: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 22: ...1 Electric diagram Sirocco 55 80 110 single phase...
Page 23: ...2 Sirocco 110 three phase...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...