background image

14 

 connection to a ZPCE double circuit gas boiler: connect the terminals 3-6 of the terminal board, to 

terminals 3-6 of the boiler terminal board,  

 

 

 

 adjust the thermostat between to 26 and 28°C (maximum 30°C), in general set the air temperature 

1 to 2°C higher than the pool water temperature, 

 

 

 

 a post-ventilation runs for 3 minutes when the reference temperature is reduced on the thermostat 

located in the pool hall (with the “VI/VP” switch on “VI”, without any dehumidification or defrosting  
cycles in progress): check that the circulator stops. 

 

 

 

2. Troubleshooting 

2.1 Status and faults in the ECP 600 settings 

 

 

Terminals 

Description 

N - R 

mains-supply 230Vac-50Hz to the ECP600 regulator 

20 - 21 

output from compressor supply 230 Vac -50Hz  

30 - 31 

230Vac-50Hz output (not used) and protected by the ECP600 fuse 

22 - 23 

ventilator 230Vac-50Hz output 

25 - 24 

output for circulator hot water battery option 230Vac-50Hz 

26 - 27 

output alarm report 230Vac-50Hz 

28 - 29 

output contact “NO” (without polarity) control of heat source hot water battery option 

11 – 12 - 13 

Input control sensor type PTC (inlet or defrost) 

4 - 5 

power supply 12Vac-50Hz 

input 6Vac-50Hz given by the hygrostat function (request active if 6Vac-50Hz 
between 7 and 4) 

input 6Vac-50Hz given by the thermostat function (request active if 6Vac-50Hz 
between 2 and 4) 

input 12Vac-50Hz fan heat fault (shunted not active) (fault active if 0Vac-50Hz 
between 8 and 4, “défaut thermique ventilateur” led lit up) 

input 12Vac-50Hz faults BP and/or HP, and/or phase order (Sirocco three-phase) 
(fault active if 0Vac-50Hz between 9 and 4, “défaut pressostat HP ou BP” led lit up) 

10 

input 12Vac-50Hz compressor heat fault (shunted not active) (fault active if 0Vac-
50Hz between 10 and 4, “défaut thermique compresseur” led lit up) 

 

Led lit continuously 

Meaning 

“compresseur” 

= compressor 

the compressor is operational (blinking = temporisation in process) 

“EPROM” 

ECP600 regulator out of order  

 
 

Warning - low temperature: if the dehumidifier hot water battery is not supplied by a 
boiler, but by an aero-thermal or a geothermal system, the heating circuit water will be at 
a maximum temperature of 45-40°C. The power of the battery will then be considerably 
lower (3 to 4 times less) than the nominal power given for water at 90-70°C. If the power 
of the battery is lower than the heating needs of the room, plan for additional heating by 
radiator, heated floor or fan convector. 

If your pool has a cover (shutter or bubble sheet type, etc.), you can lower the room 
temperature (by adjusting the thermostat to about 20°C) when it is in place and raise the 
pool hall temperature before removing the cover. 

Terminals 3-6 can also ensure a heat source control function (see §1.3.7.4) 

EN 

Summary of Contents for SIROCCO 110

Page 1: ...Installation instructions Air dehumidifier for indoor swimming pools R f N D 005 A EN Ver 02 2010 SIROCCO 55 80 110...

Page 2: ...to surrounding air 6 1 3 5 Inset connection 7 1 3 6 Connection of the condensation drainage 8 1 3 7 Electric connections 8 1 3 8 Connection of the options 12 1 4 Commissioning 13 1 4 1 Starting the a...

Page 3: ...on studs x4 dowel x 2 long bolt x 2 For Sirocco can be inset sleeve x 2 frame with cadre suction grid and filter x 1 frame with blowing grid frame fixture kit x 1 The appliance must be transported upr...

Page 4: ...0 unit protection class Sirocco ambient IP 44 Sirocco can be inset IP 45 class I refrigerant gas R407C refrigerant charge see product information plate 1 2 2 Operating conditions operating range 10 C...

Page 5: ...installed outside volumes 0 1 and 2 the appliance has a protection index of at least IP X5 In volume 2 see figures 702A and 702B the appliances must be either class II for lighting or class I protecte...

Page 6: ...hat the materials used are compatible with a swimming pool environment the walls are sufficiently waterproofed and insulated to avoid condensation forming in the room when relative humidity reaches 60...

Page 7: ...with two bolt screws washers and plugs supplied in a solid wall Pool minimum distance Sirocco 55 80 110 suction grid blowing grid Hygro Control condensation drainage air renewal system see 1 3 2 fres...

Page 8: ...leeves and mark the two inside anchoring points install the fixing plugs into the solid wall using the marks present the appliance again and from the inside screw in the bolt screws washers into each...

Page 9: ...7 3 Cable sizes Supply cable size for cables of a maximum length of 20 metres calculation basis 5A mm this must be checked and adapted depending on installation conditions Option Voltage Nominal powe...

Page 10: ...echnician must install the device cables If the power cable is damaged it must be replaced by a qualified technician or by a Zodiac Pool Care Europe service station Main supply see 1 3 7 3 Regulation...

Page 11: ...desired relative humidity Display of the ambient temperature and or humidity by pressing once C and or RH blink To exit press or wait 10 seconds only if your appliance is fitted with the hot water ba...

Page 12: ...ll the digits light or and the appliance starts up Parameter setting in hygro thermostat or hygrostat mode Hygro Control must be on standby press and for 3 seconds hygro thermostat mode press or to se...

Page 13: ...nput to the hot water battery 45 C minimum 90 C maximum Maximum pressure water battery circuit 3 bars Power returned to the air at 27 C input to the hot water battery Connection to the primary circuit...

Page 14: ...s a heating request is active This safety device has two levels of triggering 1 by THS safety thermostat if the T C is 65 C it is automatically reset 2 if the temperature continues to increase the sec...

Page 15: ...e thermostat function request active if 6Vac 50Hz between 2 and 4 8 input 12Vac 50Hz fan heat fault shunted not active fault active if 0Vac 50Hz between 8 and 4 d faut thermique ventilateur led lit up...

Page 16: ...emperature than 5 C or than 40 C a defrosting cycle is in progress temperature is 5 C The compressor is stopped and ventilation is maintained the defrosting sensor is out of order The defrosting cycle...

Page 17: ...ol and make a shunt between terminals 1 5 7 and check the voltage between 4 5 12V Replace the ECP 600 no yes Replace the Hygro Control See faults table 2 1 The appliance does not work No fault display...

Page 18: ...o Is the appliance being ventilated all the time Voltage on the compressor terminals 230V or 400V yes Replace the contactor no no Re connect the Hygro Control and check that it is operational Wait for...

Page 19: ...teries evaporator condenser and hot water by removing the cover from the appliance switched off Depending on the condition clean with a silk brush and a vacuum cleaner 3 2 Spare parts Naming Item numb...

Page 20: ...e back to the reseller or ask the transporter to take it back This is known as a One for One exchange Otherwise please take it to a waste collection centre if your local council has set up a selective...

Page 21: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Page 22: ...1 Electric diagram Sirocco 55 80 110 single phase...

Page 23: ...2 Sirocco 110 three phase...

Page 24: ...y 230Vac 50Hz for battery circulator or used for electric logic of the heating option by electric backing E1 high pressure switch E2 low pressure switch OAE back up heating option R heating resistor T...

Page 25: ...4 Dimensions weight without option A B C Kg mm Sirocco 55 65 1030 620 653 Sirocco 80 75 1220 810 843 Sirocco 110 85 1410 1000 1033...

Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Page 28: ...Care Europe Boulevard de la Romanerie BP 90023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Global provider of innovative pool products and services Produits et services innova...

Reviews: