5.3.3.
Ignition of the fuel and boiler’s heating up
ATTENTION : before ignition of the boiler it is necessary to check the
position of the ceramic element in the combustion chamber of the boiler (it
should be centered and should touch the back vertical wall of the boiler’
combustion chamber).
•
The operating thermostat of the boiler should be set to 80
o
C or any other
temperature level of the circulating water in the hot water boiler.
ATTENTION : in order to achieve efficient wood gasification and
combustion process, it is necessary to keep the circulating water
temperature above 60
o
C;
•
Turn the set-point of the flue gases thermostat to minimal position;
•
Switch off the flue gas fan (turn into off position the START switch). The
status of the operating mode of the flue gas fan is indicated with the lamp,
mounted above this switch;
The ignition of the fuel, as well as the boiler’s heating-up is performed,
following the steps, described below:
•
Open the ignition flap – the lever for ignition flap control is positioned on
the right hand side of the upper section of the boiler, its driven manually
by pulling it;
Figure 5.3. The lever for the ignition lever of the boiler is pushed backwards
and the flap is closed.
•
Open the door of the fuel hopper of the boiler, arrange the igniters and
make a pile above the orifice of burner, make the pile scarce, so the flue
gases could easily pass through the burner’s nozzle. Open the door of the
fuel hopper, arrange a pile of chopped wood particles (preferable dry pine
Lever, which moves the
ignition flap
NOTE:
the
figure
shows closed position of
the ignition flap;