p. 19/69
•
To the chimney;
•
Fire prevention requirements;
•
To the power circuit - EN 60335-1/1997- “Household and similar
electrical appliances – safety, Part 1 – General requirements”;
•
The ambient air inflow orifice of the boiler’s room should have cross
section of minimum 0.04 m
2
;
4.2.
Basic requirements for installation of wood gasification hot water
boiler of series “Pyrotherm”, considering it’s easy maintenance and
servicing:
o
The boiler should be installed on thermally safe and
noncombustible pad, which should have height of 50 mm;
o
The minimal space in front of the boiler for cleaning, maintenance
etc, should be 1000 mm;
o
The minimal distance allowed between the back side of the boiler
and a wall should be 400 mm;
o
The minimal distance from the boiler’s side and a wall should be
500 mm, in order to allow easy maintenance and servicing
procedures of the boiler’s convective heat exchanger and back side
of the unit;
o
The minimal distance between the opposite side of the boiler and a
wall should be 500 mm in order to ensure easy access to the heat
exchanger and to allow easy cleaning of the deposited ash;
o
The minimal distance between the top side of the boiler and a wall
(ceiling) should be 600 mm, in order to ensure easy access to the
control board of the unit, for attachment of the emergency coil, as
well as for the cleaning and maintenance procedures of the heat
exchanger;
EXPLANATION: after the hot water boiler is positioned, the following
procedures of the installation process should be performed:
o
The ceramic flue gas directing element should be placed in the
combustion chamber of the boiler;