9
Gas Supply
ROOM VENTILATION
An exhaust fan may be used with the appliance; in each case it shall be installed
in conformity with the appropriate national and local standards. Exhaust
hood operation may affect other vented appliances; in each case it shall be
installed in conformity with the appropriate national and local standards.
TYPE OF GAS
This appliance is shipped from the factory for use with natural gas. For use with liquid
propane gas, please follow the conversion procedure described on page 16. A step
by step conversion procedure is also included with each set of liquid propane gas orifices.
GAS PRESSURE
• The maximum inlet gas supply pressure incoming to the gas appliance pressure
regulator is 1/2 PSI.
• The minimum gas supply pressure for checking the regulator setting shall be at least 1"
W.C.P. (0.25 kPa) above the inlet specified manifold pressure to the appliance. This
operating pressure is 4" W.C.P. (1 kPa) for natural gas and 10" W.C.P. (2.75 kPa) for
liquid propane gas.
• Gas range top requires 1"–6" (25–152 mm) side wall spacing above the counter
height for proper combustion. Please review specific model installation instructions for
required dimensions; 30"–36" (762–914 mm) between the range top and bottom of
the range hood above, 1/4" (6 mm) for sides below countertop height.
NOTE
: Please consult your local building codes for variations with installation.
BEFORE INSTALLATION