Front panel controls and indicators
The following table gives an overview of the front panel controls and indicators.
Operational features described here are not available to all users. Further
information on control panel operation and access restrictions can be found in
the topic “Control panel operation” on page 14.
Table 2: Front panel controls and indicators
Control/LED LED
colour
Description
Supply LED
Green
Indicates that the system is powered up.
General Test LED
Yellow
Indicates that one or more features or devices are
being tested.
General Disable LED
Yellow
Indicates that one or more features or devices are
disabled.
General Fault LED
Yellow
Indicates a general fault. The fault LED for the
corresponding device or feature also flashes.
Alarm LED
Red
Indicates a fire alarm.
A flashing LED indicates that the alarm was
activated by a detector. A steady LED indicates that
the alarm was activated by a manual call point.
Fire Routing
On/Acknowledged
button and LED
Red
Cancels a previously configured delay as it counts
down and activates fire routing.
A flashing LED indicates that fire routing has been
activated. A steady LED indicates that the fire
routing signal has been acknowledged by the
remote monitoring equipment.
Fire Routing Delay
button and LED
Yellow
Enables or disables a previously configured fire
routing delay. Cancels a delay as it counts down
and activates fire routing.
A steady LED indicates that a delay is configured
and enabled. A flashing LED indicates that a delay
is counting (fire routing is activated when the
configured delay elapses or when the delay is
cancelled).
Fire Routing
Fault/Disabled/Test
LED
Yellow
Indicates a fire routing fault, disablement, or test.
A flashing LED indicates a fault. A steady LED
indicates a disablement or a test.
Fire Protection
On/Acknowledged
button and LED
Red
Cancels a previously configured delay as it counts
down and activates fire protection.
A flashing LED indicates that fire protection has
been activated. A steady LED indicates that the fire
protection signal has been acknowledged by the
remote monitoring equipment.
4
ZP2-F Series Fire Alarm Control Panel Operation Manual