Condition Description
Maximum loops exceeded in a
network
The number of loops in a fire network exceeds the
maximum allowed (32)
Maximum conventional zones
exceeded in a network
The number of conventional zones in a fire network
exceeds the maximum allowed (64)
Prealarm
A device (and corresponding zone) is in prealarm
Alert
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
Configuration device connected
A control panel configuration session is initiated via an
external device (PC, laptop etc.)
Date and time not set
The system started but the date and time are not set
Event log full
The control panel event log is full
In addition to the above, the following system status events are also added to the
event log (but are not included in the control panel current events report).
Table 5: Other system status events added to the event log
Event Description
General system events
The control panel is reset, the panel is silenced, a new date
and time is set, the system is initiated etc.
User sessions
The date and time information for activation and termination
of user sessions
Actions
An output group is activated or deactivated or a
programmable system command is executed (via the
Configuration Utility)
Rules activation
A rule is activated [1]
Conditions deactivation
A system condition is deactivated
Power supply faults eliminated
A previously logged power supply fault is resolved
[1] A rule consists of one or more states (combined by Boolean operators) that are configured to
trigger specific system actions after a specific confirmation time. Rules are created by your
installation or maintenance contractor using the configuration utility.
Summary of status indications
This section includes a summary of the control panel status indications.
Standby
Standby is indicated as follows:
• The Supply LED is steady
• If a sounder delay has been enabled the Sounder Delay LED is steady
• If a fire routing delay has been enabled the Fire Routing Delay LED is steady
• If a fire protection delay has been enabled the Fire Protection Delay LED is
steady
10
ZP2-F Series Fire Alarm Control Panel Operation Manual