Indication of remote and local events on the LCD
The local control panel ID is always displayed on the LCD (see Figure 2 on
page 7).
If your control panel forms part of a fire network, the event notification includes
the panel ID reporting the event as follows:
• If the panel ID matches the local ID, then the event relates to the local control
panel.
• If the panel ID does not match the local ID, then the event is reported by the
remote control panel with the panel ID indicated.
Note:
Repeater panels are installed only in fire networks and by default have a
network board installed. Fire alarm control panels must have a network board
installed to connect to a fire network.
Acoustic indicators
The control panel uses the following acoustic indicators to highlight system
events.
Indication Description
The buzzer sounds continuously
Indicates a fire alarm or a system fault
The buzzer sounds intermittently (long tone) [1] Indicates all other faults
The buzzer sounds intermittently (short tone) [1] Indicates a condition
[1] A long tone is 50% ON and 50% OFF. A short tone is 25% ON and 75% OFF.
Summary of conditions
System events logged as conditions are shown below.
Table 4: System events logged as conditions
Condition Description
Tests
A control panel feature or device is being tested
Disablements
A control panel feature or device is disabled
Sounder, fire routing, and fire
protection delays
A sounder, fire routing, or fire protection delay is enabled or
disabled
Loop device not configured
A loop device is detected that is not configured
Input activation
An input is activated (subject to configuration)
Output group activation
An output group is activated
New node in the fire network
A control panel has been added to the fire network
ZP2-F Series Fire Alarm Control Panel Operation Manual
9