804050UK G4 Commercial chilled and sparkling installation instructions - Sept. 2016 - v3.02
Page 11 of 20
Section 1
Ventilation
Important
See section 3 Command-Centre
TM
installation, pages 14 to 15
Vent cut-out details
A
Air outlet vent
B
Air inlet vent
1.2 Preferred ventilation arrangements for CS models
The ducted vent kit supplied with the Command-Centre
TM
exhausting through the kick-space should be used,
to provide adequate ventilation in all conditions. (Ancillary components are not shown in these diagrams).
C
Ducted vent
1.1 Ventilation for all models
•
The clearance envelope dimensions stated in the specification sheets and installation instructions must
be observed.
•
Adequate ventilation must be provided to ensure that the cupboard space temperature does not exceed
35
0
C.
B
A
C
100mm min.
Cupboard back must be fully
closed to prevent recirculation
into cupboard from kick space.
A