TR400
12360-0706-05
Page
8 / 12
www.ziehl.de
Setup *
Mode Function
Alarm select
Sensor
select
Display
SET
Factory Adjust
0
Switching Point (°C)
Relay 1…4 Sensor 1…4 -199°…800°C
Store
100 °C
group *
1)
Alarm 1 = Sensor 1…3
Alarm 2 = Sensor 1…3
Alarm 3 = Sensor 4
Alarm 4 = Sensor 4
1
Hysteresis (K)
Relay 1…4
-
1 …99 K
Store
3 K
2
tALARM (s)
Relay 1…4
-
0,1 … 99,9 s
Store
0,1 s
3
tALARM off (s)
Relay 1…4
-
0 … 999 s
Store
0 s
4
autoreset - locked
Relay 1…4
-
0 = autoreset
Store
0 = autoreset
1 = locked
5
Operating function
Relay 1…4
-
Max-NO contact
Sensor alarm
Store
Max-NC contact
Min-NO contact
Min-NC contact
6
Sensor connection
-
sensor 1…4
3-.L
3-wire
3-.L
Store
not connected
n.c.
*
3
2-
wire (Ω)
0…99,9
7
Analog out
Out 1 = 1
sensor 1…4 0 = 0…20 mA
Store
Out 1 = group 1+2+3
Out 2 = 2
group *
1)
*2)
0 = 0…10 V
Out 2 = sensor 4
4 = 4…20 mA
4 = 2…10 V
Zero
-
-
-
199°…800°C
Store
0 °C = 0 mA
FullScale
-
-
-
199°…800°C
Store
100 °C = 20 mA
8
Sensor Simulation
-
sensor 1…4 -199°…800°C
-
9
Code safe = off
-
-
500 (safe)
500
Code safe = on
504 (free)
on/off/on
A
USB
Config To TR
= 2
-
Start
Config To USB
= 3
Start
Firmware
Update = 4
(+ button Reset) -> Start
* return within 30 s without any button pushed
*
1)
group: - sensor 1+2+3, - sensor 1+2+3+4, - sensor 1+2, - sensor 3+4
*
2)
When a group of sensors is selected, the warmest temperature makes the signal for the analog output.
*
3
) not connected (no sensor connected)
8
Trouble shooting
•
LED Sensor Error
The LED sensor error indicates a failure at a sensor and the sensor-LED blinks. The sensor alarm relay
K7 has switched. Refer to operation mode 5. Also see analog output.
•
Display
EEE
sensor interruption or over-range
-EE
sensor short circuit or under
–range
•
Analog output 0 mA/0 V
If sensor failure short circuit or sensor interruption is detected the output current is 0 mA and the output
voltage 0 V.