background image

TR400  

12360-0706-05

  

Page

 

11 / 12 

www.ziehl.de 

  

EMC-tests 

EN 61326-1 

 

emitted interference 

EN 61000-6-3 

 

Burst 

EN 61000-4-4  +/-4 kV 

 

Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms 

 

SURGE 

IEC 61000-4-5  +/-4 kV 

 

Impulse 1,2/50 µs (8/20 µs) 

 

discharge of static electricity 

IEC 61000-4-2  

+/-4 kV contact, 

 

+/- 8kV air 

 

 

Environmental conditions 

 

 

Ambient temperature range 

-20 °C ... +65 °C 

 

Storage temperature range 

-

20 °C … +70 °C 

 

Altitude 

Up to 2000 m 

 

Climatic conditions 

– 85 % rel. humidity, no condensation 

 

External wiring temperature ran 

-

5 °C … +70 °C 

 

Vibration resistance EN 60068-2-6 

2…25 Hz ±1.6 mm 

 

25 ... 150 Hz 5 g 

 

 

Galvanic insulation / Test-voltage 

Us  

–  Relays, sensors, USB, analog output, Reset 

input  ->  DC 3820 V 

 

Relays  

–  sensors, USB, analog output, 

Reset input  

->  DC 3820 V 

No galvanic insulation 

sensors, USB, analog output, Reset input 

 

 

Reset input Y1/Y2 

app. DC 18 V / 3,5 mA   

 

 

USB connector   

Typ A, for connecting a USB stick 

 

configuration / firmware update 

 

 

Housing 

Type V8 

Dimensions (H x W x D) 

140 x 90 x 58 mm 

Mounting height / Width 

55 mm / 8 TE 

Line connection solid wire 

je 1 x  1,5 mm

2

 

Stranded wire with isolated ferrules 

je 1 x  1,0 mm

2

 

Torque 

0,5 Nm (3,6 lb.in) 

Protection class housing 

IP 20 

Protection class terminals 

IP 20 

Fitting position 

any 

Mounting 

Snap mounting on 35 mm standard rail  

 

EN 60715 or M4 screws 

Weight 

app. 360 g 

 
 

Subject to technical modifications 

 
 
 

 

Summary of Contents for TR400

Page 1: ...de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual TR400 updated...

Page 2: ...ts 1 Application and short description 3 2 Overview of functions 3 3 Connection plan 3 4 Display and operating elements 4 5 Function diagram 4 6 Important notes 5 7 Assembly 6 8 Putting into operation...

Page 3: ...rature monitoring wherever up to 4 different measuring points must be monitored simultaneously motors and generators with simultaneous monitoring of bearings and coolant transformers with additional m...

Page 4: ...sor 3 4x LED Alarm 4 Select buttons 5 Display 3 digits 6 Up button 7 Down button 8 Mode button 9 Set button 10 Display 1 digit Mode 11 Reset button 12 Terminal for USB Stick 4 Function diagram sensor...

Page 5: ...sensors must be connected to the plug in terminals 1T1 1T2 1T3 etc To ensure proper operation this plug in terminals have gold plated contacts Do not use these plugs for other terminals The measuring...

Page 6: ...tion file from USB Stick to TR400 settings of a readily configured TR400 can be easily read out and transferred to other TR400 The USB Stick is necessary for configuration and for firmware updates onl...

Page 7: ...lue of the compensation line resistance RK must be calculated as follows RK n 1 x RL 2 RL line resistance of two wires n number of sensors Sensor Simulation At this menu item a sensor or sensor group...

Page 8: ...nsor 4 4 4 20 mA 4 2 10 V Zero 199 800 C Store 0 C 0 mA FullScale 199 800 C Store 100 C 20 mA 8 Sensor Simulation sensor 1 4 199 800 C 9 Code safe off 500 safe 500 Code safe on 504 free on off on A US...

Page 9: ...ruption of power supply ATTENTION There is a short alarm signal of K7 when switching on the supply voltage Sensor alarm relay K7 with operating function 1 NO contact picks up at any failure ATTENTION...

Page 10: ...ance 1 of programmed span 1 C Relay Data K1 K4 and K7 5 x 1 change over contacts Switching voltage max AC 415 V Switching current max 5 A Switching capacity max 1250 VA resistive load max 120 W at DC...

Page 11: ...150 Hz 5 g Galvanic insulation Test voltage Us Relays sensors USB analog output Reset input DC 3820 V Relays sensors USB analog output Reset input DC 3820 V No galvanic insulation sensors USB analog...

Page 12: ...en f r unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung 4 2 mm for fixing to wall with screws 4 2 mm Sie finden diese und weitere Betriebsanleitungen soweit verf gbar a...

Reviews: