TR400
12360-0706-05
Page
10 / 12
www.ziehl.de
9
Technical data
Rated supply voltage Us
AC/DC 24
– 240V
Tolerance
DC 20,4 - 297 V
AC 20 - 264 V 50/60 Hz
Power consumption
< 4 W
< 13 VA
Sensor connection (4 sensors)
Pt 100 (RTD) acc. to EN 60751 (2/3- wire)
Measuring range
-199°C .. 800°C,
resolution = 1°C
Resistance of wire.
max. 500 Ohm
Sensor current
≤0,7 mA
Measuring cycle/ time sensor
≤ 1,5 s
Tolerance
±0,5 % of measured value ±1 digit
Temperature factor
<0,04°C/K
Analog outputs
OUT 1 and OUT 2
Voltage-output
DC 0/2 V
– 10 V, max. DC 10 mA
Current output
DC 0/4 mA
– 20 mA
Load
max. 500 Ω
No-load voltage
max. DC 16 V
Tolerance
1% of programmed span ±1 °C
Relay-
Data K1 … K4 and K7
5 x 1 change-over contacts
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching capacity
max. 1250 VA (resistive load)
max. 120 W at DC 24 V
UL electrical ratings:
250 V ac, 5 A, resistive
E214025
240 V ac, 1/2 hp
120 V ac, ¼ h
B 300
– pilot duty, UL 508
Nominal operational current Ie
AC15
Ie = 3 A
Ue = 250 V
DC13
Ie = 2 A
Ue = 24 V
Ie = 0,2 A
Ue = 125 V
Ie = 0,1 A
Ue = 250 V
Recommended fuse NO
4 A time-lag or miniature circuit-breaker MCB B4
Recommended fuse NC
3,15 A time-lag
Expected contact life mechanical
3 x 10
7
operations
Expected contact life electrical
1 x 10
5
operations at AC 250 V / 6 A
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
III
Contamination level
2
Rated insulation voltage Ui
300 V
On-time
100 %