Reset to factory adjust
When pushing the buttons "Reset" and "Set" simultaneously > 5 s all programmed parameters will be
set back to factory adjust. Code save must be off. If code save is on, see mode 9.
•
No parameter setup possible - Code save on
Code save protects the relay against unauthorized manipulations. With code save on no programmed
parameters can be changed. The factory code is 504 and cannot be changed by the user. See setup
mode 9.
•
Failure display "E 0"
or “E 2”, Sensor error relay K7 switching
Operation failure. Switch off the supply voltage and restart. When the failure is still going on, the relay
should be replaced and send to the factory.
•
Failure display "E 1" or "E 2", Sensor error relay K7 switching
EEPROM parameter failure. Check all programmed parameters and setup new when necessary. Switch
off the supply voltage and restart again. When the failure is still going on, the relay should be replaced
and send to the factory.
•
Sensor Alarm Relay K7
Sensor alarm relay K7 with operating function 2 = NC-contact releases at any failure and signals an
interruption of power-supply.
ATTENTION: There is a short alarm-signal of K7 when switching-on the supply-voltage.
Sensor alarm relay K7 with operating function 1 = NO-contact picks up at any failure.
ATTENTION: There is no alarm-signal of K7 if interruption of power supply occurs.
•
Indication of the firmware-version
: Push „Set“ for 4 s in the display mode.
•
USB Stick
– Error when writing configuration-file to USB-Stick
: The file „TR600.cfg“ is being
created or overwritten. In addition a file „TR600_xx.cfg“ is being created. „xx“ stands for a continuous
index (00 … 99).
•
USB Stick
– Error when reading configuration-file from USB-Stick
: The file „TR600.cfg“ must be in
the main directory. Parameters in this Text-file can be changed (text editor) and adapted to the
required configuration.
•
USB Stick
– Error when executing firmware-update
: The 2 yellow LEDs OUT 1 and OUT 2 display
state of update.
LED OUT 1
LED OUT 2
Description
blinking
on
no firmware on TR400
on
off
new firmware is loaded to TR400
on
on
TR400 has called the update
blinking
off
no (no valid) firmware on USB- Stick (TR400.hex)
blinking
blinking
USB- Stick not identified
If a firmware-
update fails (TR doesn’t start as usual, display is dark) the update can be re-started as
follows:
Switch off Us, keep buttons „Up“ (▲) and „Set“ pressed and switch on Us
-> Firmware-update starts.