Log description:
Measurement data log
Time specification, can be set with [Interval] selection box,
every 10s (4h recording period),
30s (12h), 1min (25h), 5min (5 days), 10min (10 days),
30min (31 days), 1h (62 days), 2h (125 days), 5h (312
days), 10h (625 days), 12h (750 days), 24h (1500 days)
Alarm log
When there is a change in the alarm state
Content of the log files
⇒
Individual data records
Min/Max values with date/time
⇒
Date/time; Measurement values sensors 1-8; Alarm
values 1-4 (sum of the sensors that triggered the alarm
S1=1, S2=2…S8=128); Error number (device error)
8.17 View measurements and alarms, sensor simulation
Here, all measurements can be clearly viewed with min./max. values plus the alarms. Using the
sensor simulation, individual sensor values can be simulated. The simulation independently
switches off after 15 minutes with no changes in the simulation value.