5. Important Informations
To use the equipment flawless and safe, transport and store properly, install and start
professionally and operate as directed.
Only let persons work with the equipment who are familiar with installation, start and use
and who have appropriate qualification corresponding to their function. They must observe
the contents of the instructions manual, the information which are written on the equipment
and the relevant security instructions for the setting up and the use of electrical units.
The equipments are built according to DIN / EN and checked and leave the plant according
to security in perfect condition. To keep this condition, observe the security instructions with
the headline „Attention“ written in the instructions manual. Ignoring of the security
instructions may lead to death, physical injury or damage of the equipment itself and of other
apparatus and equipment.
If, in any case the information in the instructions manual is not sufficient, please contact our
company or the responsible representative.
Instead of the industrial norms and regulations written in this instructions manual valid for
Europe, you must observe out of their geographical scope the valid and relevant regulations
of the corresponding country.
ATTENTION
Dangerous electrical voltage!
May lead to electrical shock and burn.
Before beginning of work switch unit and equipment free of voltage.
Observe the maximum temperature permissible when installing in switching cabinet.
Make sure sufficient space to other equipment or heat sources. If the cooling
becomes more difficult e.g. through close proximity of apparatus with elevated
surface temperature or hindrance of the cooling air, the tolerable environmental
temperature is diminishing.
ATTENTION! Connection of sensors
The inputs 1T1, 1T2, 1T3 to 8T3 and RESET Y1, Y2 are not potentially
separated from output RS485. Temperatur-sensors must have
a sufficient insulation.
Only signals according to SELV (Safety Extra Low Voltage) may be
connected.
The pluggable terminals of the measuring inputs have a special
contact-material and may only be used for the connection of the
sensors.
Attention! Universal power supply
The unit is equipped with an universal power supply, that is suitable for DC- and AC-
voltages. Before connecting the unit to the current, make sure that the allowed scope of
voltage of the control voltage Us, written on the lateral type plate, corresponds to the supply
voltage of the unit.
!