(Date / Name): 16.04.2009 Sc
Drawing no.: 12280-0701-00
Page 22 of 24
Name: TR 800 WEB
ZIEHL industrie-elektronik GmbH + Co KG, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, email: [email protected]
13. Technical Data
Rated supply voltage Us
AC/DC 24 – 240 V 0/45-120 Hz < 4 W < 8 VA
Toleranz
DC 20,4 - 297 V
AC 20 - 264 V
Relay output
4 x 1 Wechsler (CO)
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching capacity
max. 2000 VA (ohmic load)
max.120 W bei DC 24 V
Reduction factor for cos
φ
= 0,7
0,5
UL electrical ratings:
250 V ac, 3 A, general use
240 V ac, 1/4 hp, 2.9 FLA
120 V ac, 1/10 hp, 3.0 FLA
C 300
D300 1 A 240 VAC
Nominal operational current Ie
AC15
Ie = 3 A
Ue = 250 V
DC13
Ie = 2 A
Ue = 24 V
Ie = 0,2 A Ue = 125 V
Ie = 0,1 A Ue = 250 V
Recommended fuses for contact
T 3,15 A (gL)
Expected contact life mechanical
3 x 10
7
operations
Expected contact life electrical
1 x 10
5
operations at AC 250 V / 6 A
Test conditions
EN 61010-1
Rated impulse voltage
4000 V
Contamination level
2
Rated insulation voltage Ui
300 V
On-time
100 %
rated ambient temperature range
-20 °C ... +65 °C
EN 60068-2-2 dry heat
Vibration resistance EN 60068-2-6
2…25 Hz ±1,6 mm
25 ... 150 Hz 5 g
Galvanic insulation (test voltage)
ethernet – sensors
DC 750 V
Us – relays, sensors, ethernet
DC 3820 V
relays – sensors, ethernet
DC 3820 V
sensors – relays
DC 3820 V
No galvanic insulation
RS485 – sensors – Reset-inputY1/Y2
EMC-tests
EN 61326-1
emitted interference
EN 61000-6-3
Burst
EN 61000-4-4 +/-4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
SURGE
IEC 61000-4-5 +/-1 kV
Impulse 1,2/50 µs (8/20 µs)
discharge of static electricity
IEC 61000-4-2 +/-4 kV contact,
+/- 8kV air
Network-connection
10/100 MBit Auto
-
MDIX
Max. number of connections
http/https = 5
Real-time clock
time-reserve 7 days