3.4.2
Period of s standstill period
The maximum permissible storage duration or standstill period without line supply is especially
dependent on the electric capacitors, because the dielectric material in the capacitor degrades and
the electrolyte evaporates.
Depending on the period without line supply, it must carry out a reformation of the internal capacitors
before applying line voltage to the inverter.
Period without
line supply
Action before start-up
under 1 Year
none
1 - 2 Years
Device for 1 hour without enable connected to line
longer than 2 years
Reformation (without enable) by adjustable voltage supply
1. For 1 hour of 30% of the line voltage
2. For 1 hour of 60% of the line voltage
3. For 2 hours of 85% of the line voltage
4. For 3 hours of 100% of the line voltage
Line voltage
F
Technical data, for wide voltage range = higher value of line
voltage indication
3.5 Waste disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance with the legal
stipulations.
4Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect
in the device due to assembly errors or environmental in
uences:
•
Before installation remove the device from the packing and check for any possible shipping
damage!
•
Assemble the device on a clean and stable base. Do not distort during assembly! Use the
appropriate mounting devices for proper installation of the unit!
•
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock
loads. Any banging shut of doors that are integrated into these lightweight walls, can result in
extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
•
Maintain the stated minimum clearances to ensure unobstructed cooling- air feed as well as
unobstructed outgoing air discharge (
F
minimum space requirement)!
•
The plastic washers must be installed between the screw heads and the housing for models
with mounting holes on the inside of the housing!
•
The device should be installed in a location where it will not be disturbed, but at the same time
can be easily accessed!
•
Depending on the housing model cut off necessary cable inlets respectively to the cable
diameter. Or alternative use cable inlet for cable glands. Metal sheet housings are supplied with
stoppers. Any cable ducts openings not used must be sealed!
•
Care must be taken to avoid direct radiation from the sun!
•
The device is designed for vertical installation (cable inlet down). A horizontal or reclined
installation is only permissible after technical release of the manufacturer!
•
Be sure to observe proper heat dissipation (
F
Technical data, heat dissipation).