Information
•
Pay attention to suf
cient distance from powerlines and motor wires (min. 20 cm)
•
Do not use wire shield
•
Except the data link " D+" , " D-" and " GND" - connection may no further cable cores of
the data line be used.
•
Max. allowed wire length 1000 m (CAT5/7 500 m)
Default interface parameter
Baud rate
= 19200
Bits
= 8
Patity
= Even (None, exception of devices agriculture)
Stop bits
= 1
Handshake
= none
Information
If any matters are unclear, please contact our V-STE support department for control systems -
ventilation technology. The information sheet "Network structure of Modbus" R-TIL08_01 contains
detailed information about Modbus.
5.14.3
LON
®
Bus system is possible via add-on module
Connection to the LON
®
bus system is possible via add-on module type
“
Z-Modul-L
”
(Part-No.
380053). Communication to controller via the RS-485 interface, FTT-10A transceiver.
5.15 Potential at control voltage connections
The control voltage connections (< 50 V) relate to the joint GND potential (Exception: Relay contacts
are potential free). There is a potential separation between the control voltage connections and the
earthed conductor. It must be ensured that the maximum external voltage at the control voltage
connections cannot exceed 50V (between
“
GND
”
terminals and
“
PE
”
earthed conductor). If necessary,
a connection to the earthed conductor potential can be established, install bridge between
“
GND
”
terminal and the
“
PE
”
connection (terminal for screening).
Operating Instruction
Econtrol
–
model series EXDM
Electrical installation
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
16/85