9.9.7
Minimum speed cut off
Msco.
This function is primarily signi
cant for installation of the device as a pure P
Controller in refrigeration and air-conditioning technology.
For operation mode speed controller
1.01
without function!
Msco = OFF
(factory setting)
If no
“
Min. speed
”
is adjusted, the fan stops with
reaching the desired value.
If
“
Min. speed
”
is adjusted (e.g. 20%), then no
disconnection of the fan takes place. I.e., al-
ways a minimum ventilation is ensured (fan
does not go under setting
“
Min. speed
”
).
Msco. e.g. -2.0 K
It takes place a disconnection from setting
“
Min.
speed
”
to
“
0
”
, if the given difference is reached
related to the desired value.
At a plus value (+) before reaching the desired
value
At a minus value (-) after falling below the de-
sired value.
nM
50 %
100 %
I
Min.
Min. 35 %
Max. = 100 %
20 °C
S
7 K
R
27 °C
-2.0 K
10.05.2007
v_min_luft_abschalt.vsd
Minimum speed cut off (idealized principle diagram)
nM Motor speed
S Setpoint
R Pband
I Actual value
9.9.8
Second Group
Group 2 ON value
Second group
“
indirectly controlled
”
(picture A)
Analog output
“
AnalogOut 1
”
in IO Setup function
|
5 A
|
= group control is
programmed. This output is employed as the default signal for a speed
controller. If the default signal or the regulation deviation exceeds the group 2
switch-on point, group 1 is reduced to
“
n-min group 2
”
. Starting here, both
groups run parallel at maximum power.
Second group
“
100 % energized
”
(picture B)
Relay output (K1 or K2) in IO Setup function
|
8 K
|
= group control is pro-
grammed. A contactor is triggered via this relay contact, which directly
switches the fans of the second group to mains voltage. If the default signal or
the regulation deviation exceeds the
“
Group 2 ON value
”
switch-on point, the
relay for the second group switches on and the speed of the
rst group is
lowered to an adjustable minimum value. After that, the speed of the
rst
group increases back up to maximum.
nmin at Group2
Controller
Master
N
Si/ Se
A
Controller
Slave
Si 0-10 V
N
0 .. 100 %
1
2
0 .. 100 %
Controller
Master
N
Si/ Se
B
C
ON / OFF
N
0 / 100 %
1
2
0 .. 100 %
10.05.2007
v_zweite_gruppe.vsd
N Line
Si Signal
Se Sensor
C Contactor
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
50/85