Further menus see chapters:
•
Controller Setup
•
IO Setup
•
Limits
•
Motor Setup
•
Diagnostic
|
4E
|
E1/E2 automatic higher level
9.2 Temperature control
2.01
..
2.05
9.2.1
Basic setting
2.01
...
2.05
Base setup
Base setup
Mode
Mode
Mode selection e.g.
2.01
E1 Analog In
E1 Analog In
In all group 2 operating modes (2.01, 2.02, 2.03, ....)
“
E1 analogue In
”
factory set to
“
TF
”
(measuring range -27...+75
°
C).
Alternative selection Sensor:
“
MTG120V
”
Aktive sensor with 0 - 10 V output (
F
jumper or switch for input signal) and
proportional measuring range: -10...+120
°
C.
Alternative selection signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA (
F
jumper and/or
switches for input signal) accordingly inserted. The sensor measurement-
range must be entered in order to correctly display the actual value.
Example with a 0 - 10 V sensor and 0 - 100
°
C measurement range:
E1 Analog In = 0 - 10 V, E1 Min. = 0.0
°
C, E1 Max. = 100.0
°
C, E1 Decimally =
1, E1 Unit =
°
C
E1 Offset
E1 Offset
Sensor calibration with calibrated comparison device
E2 Function
E2 Function
•
Funktion
|
1E
|
= External Setpoint via external signal (0 - 10 V) instead of
“
Setpoint1
”
.
–
For sensor type
“
E1 Analog In
”
=
“
TF
”
: 0 - 10 V
≙
-27...+75.0
°
C.
–
For sensors with active signal: 0 - 10 V
≙
0 - 100 % sensor measuring
range.
•
Function
|
2E
|
= External manual operation via external signal (0 - 10 V).
Switch over between settings on the device and external manual
operation via digital input (
F
IO Setup).
•
Function
|
7E
|
Measurement value = Measurement value e.g. for limit
indication, display in Info menu
“
E2 Actual
”
.
Operating Instruction
Econtrol
–
model series EXDM
Programming
L-BAL-E008-GB 0945 Index 005
Part.-No. 00156742-GB
25/85