Lift the fan out of the packaging with a lifting gear (lifting beam). Attachment points are
solely the holes on the housing
fl
ange, motor bed, support plate, motor suspensions,
fastening brackets and any crane eyes of the fan (depending on the design of the fan).
•
The chain/rope may not touch the impeller and the possibly mounted frequency
inverter when lifting with the lifting beam, otherwise damage is possible.
•
The custom designs must suit the prevailing conditions.
•
Take into account easy access for cleaning and maintaining the fan.
•
Before installing the fan, make sure the safety distances are maintained compliant
with EN ISO 13857 or in household equipment according to EN 60335.
–
If the mounting height (danger area) above the reference plane is greater than or
equal to 2700 mm and is not reduced by auxiliary means such as chairs, ladders,
working platforms or
fl
oor space on vehicles, a guard grille is not necessary on the
fan.
–
If the fan is located in danger zone, then the manufacturer or operator shall ensure
that hazards shall be prevented by appropriare protective constuctions which meet
the requirements to EN ISO 13857.
•
Tighten the fastenings with the speci
fi
ed torques.
•
Drilling chips, screws and other foreign bodies must not be located inside the device!
Before the
fi
rst switch-on, remove any items that may be present (drilling chips,
screws and other foreign objects) from the intake area - risk of injury from any objects
that may
fl
y out!
•
For fans, the alignment must be adhered to during operation, e.g. if this is indicated by
“
Oben/Top
”
.
WARNING
Parts of the rotor or the entire rotor coming loose in case of a fault (e.g.
excessive vibrations)
can result in personal injury and material damage.
"
Use guard grilles or suitable design measures for critical applications (e.g. refrigerat-
ing systems with refrigerant subject to the ordinance on hazardous substances).
4.2 Connection cable & junction box
Information
In demanding environments (wet rooms, outdoor installation), connection cables must
have water draining pipe elbows. If using a junction box, install this lower than the motor
to ensure that water cannot penetrate through to the controller housing from the
connection cables.
Assembly instructions
ECblue
Mounting
L-BAL-F056-GB 2022/45 Index 005