Icontrol / Fcontrol Basic: Example for Mode
1.01
with Setting signal 0 - 10 V
[Hz]
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
24.09.2009
v_e1_modus_1_hz.vsd
1
Modus 1
E1 min. = 0 %, E1 max. = 100 %
50
2
E1 min. = 20 %, E1 max. = 100 %
40
30
20
10
3
E1 min. = 20 %, E1 max. = 80 %
E1 min. = 0 %, E1 max. = 80 %
4
Modus 1
Example:
“
E1 min.
”
= 20 %
The controller begins only at approx. 20 % higher
signal with minimal modulation.
Example:
“
E1 max.
”
= 80 %
The modulation rises linear to 100 % modulation
with 80 % setting signal.
[Hz]
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
24.09.2009
v_e1_modus_2_hz.vsd
1
Modus 2
E1 min. = 0 %, E1 max. = 100 %
50
2
E1 min. = 40 %, E1 max. = 100 %
40
30
20
10
3
E1 min. = 30 %, E1 max. = 90 %
E1 min. = 0 %, E1 max. = 80 %
4
Modus 2
Example:
“
E1 min.
”
= 30 %
Only with approx. 30 % setting signal the controller
begins with approx. 30 % modulation.
Example:
“
E1 max.
”
= 80 %
Over 80 % setting signal the modulation is switched
to 100 % modulation.
Idealized principle diagrams for setting:
“
Min. Speed
”
= 0.0 Hz and
“
Max. Speed
”
= 50.0 Hz
Operating Instructions
AM-PREMIUM(-W)
–
model series
Programming
L-BAL-E095-GB 1618 Index 006
Part.-No.
54/90