9.4.2
Setting for operation modes
4.01
...
4.03
•
4.01
pressure control, setpoint in Pa
•
4.02
and
4.03
Pressure control for ventilation systems setpoint depending on outdoor temper-
ature
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Setpoint2
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IOSetup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 100 Pa
ECblue
Min. Speed
Min. Speed
Setting range: 0 rpm...
“
Max. Speed
”
Factory setting: 0 rpm
Max. Speed
Max. Speed
Setting range: Rated speed ...0 rpm (takes priority over setting
“
Min. Speed
”
)
Factory setting: Rated speed
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed manual
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0 rpm...Rated speed, Factory setting: 200 rpm
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Icontrol / Fcontrol Basic
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup).
Factory setting: 0.0 Hz
Active in every control mode, priority by
“
Max. speed
”
.
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup)...
“
Min. Speed
”
Factory setting: 50.0 Hz
Active in every control mode!
Settings by
“
Max. frequency
”
are possible but are not made!
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Operating Instructions
AM-PREMIUM(-W)
–
model series
Programming
L-BAL-E095-GB 1618 Index 006
Part.-No.