WNS Series horizontal Oil-fired (Gas) Boiler

 

 

 

-7- 

change a new one. 
3.10 Loss voltage protection 
        While normally running boiler, the electric network may have no power or the voltage  is 
dropped  suddenly  because  of  one  certain  reason,  boiler  will  stop  running.  When  electric 
network is back to normal condition, the boiler unit will not start operation automatically. Now 
should  push  the  burning  start  button  again,  then  boiler  can  continue  running  again  so  as  to 
avoid bad result. 
3.11 Valve leakage protection 
        When there are leakages inside gas pipeline, insure the burner no start. 
3.12 Low gas pressure protection 
        When the gas pressure inside pipeline is lower than set point, insure burner no start. 
3.13 Low wind pressure protection 

When  the  fan  appear  too  low  wind  pressure  because  of  a  certain  reason,  will  cut  off 

burning automatically or burner no start. 

 

Ⅳ、

Boiler work principle 

The boiler tubes of  heating surface and furnace absorb the heat of  firing oil, transfer  it to 

the boiler water, and when the water change to steam because of heating, steam will be up and 
enter into the  vapor space  because  its specific gravity  was  reduced, and the  left  space will  be 
made  up  by  the  water  with  more  heavy  specific  gravity,  so  this  process  will  form  a  natural 
steam-water  circulation.  When  the  water  level  become  lower  because  water  changed  into  the 
steam  continuously,  the  water  pump  will  feed  water  into  the  boiler  so  as  to  keep  it  in  the 
normal water level. The above-mentioned process continues, steam will continuously produced 
by heating the water by absorbing the afterheat of firing oil. 
 

Ⅴ、

Operation Manual of Gas Fired Boiler 

 

Please refer to the Operation Manual of Gas Ffired Boiler that we provide for you. 

 

Ⅵ、

Operation requirements 

 

Preparation before operating 
Before operating, please check all boiler parts carefully, the detail is as following: 

1.1

 

Whether the manhole and hand-hole is sealed, whether the fitting parts is safety. 

1.2

 

Whether the fitting parts is safety. 

1.3

 

Whether the damper is very agility. 

1.4

 

Whether the steam pipeline, feeding water pipeline, fuel oil & gas pipeline is sufficient. 

1.5

 

Whether all control switch of control box is set on the location 

OK

 

Boiling out for boiler 
After finishing install & inspection for all boiler parts, confirm they are safety, then can do 

boiling out for boiler. 
2.1 In general, the boiling out for new boiler should be performed before starting the unit. It is 
mainly remove the  impurity and oil dirt inside boiler. While boiling out for boiler, should add 
some suitable chemical medicine, make boiler water become alkaline water and remove oil dirt 
and impurity. 
2.2  Boiling  out  for  boiler  can  use  the  chemical  medicine  of  Na

2

CO

3

  or  Na

3

PO

4

·

12H

2

O, 

compound the above medicine with water as the uniform solution with concentration of 20%. It 
is not permitted that add the solid medicine into boiler directly. 

Medicine quantity (kg/m

3

Medicine name 

The rust is very thin 

The rust is very thick 

NaOH 

2

3

Summary of Contents for WNS Series

Page 1: ...l Gas fired Oil Boiler ZhangjiagangWilfordThermalTechnology Co Ltd Please read this manual carefully before using this machin Only qualified workers can operate this machine If the operation method is...

Page 2: ...ler structure 5 Boiler work principle 7 Operation Manual of Gas Fired Boiler 7 Operation requirements 7 Maintenance of boiler 11 Inspection hydraulic testing for pressure parts 12 Attention for users...

Page 3: ...appendix list product quality certificate one copy Installation description Preparation work before installation Check the completeness of the boiler accessories according to the packing list and the...

Page 4: ...drawings Water pump is connected with water tank if user has additional requirements can provide spare water pump 4 2 Safety valve must be assembled after hydraulic testing and connected to the tube f...

Page 5: ...r boiler water level indication and for the supervision by boiler operator The water level controller is used for transmitting the value of boiler water level The control system will control the runni...

Page 6: ...ecause of some reasons the photo resistance has no sense of light stop burning and send out acoustical light alarm continue post purging for gas fired boiler then stop running boiler Check and find ou...

Page 7: ...ill feed water into the boiler so as to keep it in the normal water level The above mentioned process continues steam will continuously produced by heating the water by absorbing the afterheat of firi...

Page 8: ...iler again according to above mentioned way Running boiler 3 1 Start and running boiler normally 3 1 1 Open the air vent valve on the top of boiler or lift the valve core of safety valve 3 1 2 Start b...

Page 9: ...warming tube should be according to the length diameter of pipeline steam temperature and so on In generally it should not less than ten minutes After the tube is heated open the main steam valve slow...

Page 10: ...it quality 6 9 The photoresistance should be removed for examination testing every three month measure the values of resistance of bright dark Photoresistance type MG41 100A Rated power capacity 100M...

Page 11: ...etter W means week Letter M means month Letter S means season Letter Y means year Blow down of boiler In generally the feeding water contains mineral matter when the water enters into boiler and after...

Page 12: ...nance if less than one month should use wet maintenance 4 1 Dry maintenance Stop running boiler drain off all boiler water remove all dirt inside boiler and clean it bake it by faint fire close all ha...

Page 13: ...ter dropping to working pressure During inspection the pressure should kept no change If find any leakage should well make record for later repairing when the pressure drop to atmosphere After hydraul...

Reviews: