WNS Series horizontal Oil-fired (Gas) Boiler

 

 

 

-10- 

6.5 Steam pressure 

Do  attention  to  the  change  of  pressure,  insure  the  steam  pressure  is  lower  than  the 

allowable highest working pressure. 
6.6 Pressure gauge 

The  bending  tube  of  pressure  gauge  should  be  washed  for  one  time  every  shift.  Check  to 

whether  the  pressure  is  in  normal  condition.  If  find  the  broken  pressure  gauge,  should  stop 
running boiler to repair it or change with a new one immediately. The pressure gauge should be 
at  least  calibrated for  one time  every  half  year to assure the  correctness of  pressure  gauge.  If 
the error is over than regulated allowable error, should repair it or change with a new pressure 
gauge. 
6.7 Safety valve 

Pay  attention  and  keep  the  safety  valve  normal  function.  In  order  to  prevent  the  sticking 

between  valve  disk  and  valve  seat,  should  pull  the  lifting  handle  of  safety  valve  to  do 
discharging steam test. This kind of testing can be done one time every 2

4 week for checking 

safety valve. 
6.8 Atomizing plate 
      The atomizing plate inside oil injector only can be cleaned by soft cloth, it is not permitted 
to  clean  it  with  hard  things.  Otherwise,  it  may  destroy  the  precision  of  atomizing  plate  and 
affect it quality. 
6.9  The  photoresistance  should  be  removed  for  examination  &  testing  every  three  month, 
measure the values of resistance of bright & dark. 
        Photoresistance type: MG41-100A 
        Rated power capacity: 100MW 
        Bright resistance value: 

100 K

Ω

 

Dark resistance value:

 

50 M

Ω

 

6.10 The boiler room should  be kept clean, water level gauge and pressure gauge should have 
good light. 
6.11 Well do the relevant work for change shift. 
6.12  In  order  to  insure  boiler  normally  running  and  lengthen  boiler  using  life  as  long  as 
possible,  should  do  daily  management  work  well  &  carefully,  for  detail,  please  refer  to 
following table: 

Daily Management

 

Period 

No 

Description 

H  D  W  M  S  Y 

Requirements 

Abnormal flameout protection 

 

 

 

 

 

During  burning  period,  close  shut  off 
valve  of  oil  (gas)  injector,  stop  oil  (gas) 
spraying 

Too low water level protection 

 

 

1   

 

 

During burning, stop feeding water, open 

blown valve, decrease water level 

Test 

Protection for unable light fire 

 

 

1   

 

 

Before  starting  boiler  automatically, 
close  shut  off  valve,  lighting  fire  no  oil 
spraying, begin time countering 

Oil (gas) pressure 

 

 

 

 

 

According  to  indication  of  inlet  oil  (gas) 

pressure gauge 

The quantity of oil spraying and 

atomizing quality 

 

 

 

 

 

Take out the oil injector, spray oil at cold 

condition. 

Inspection for photo resistance 

1   

 

 

 

 

According to the indication signal on the 

control box. 

Check                                   

Pressure regulator act 

 

 

1   

 

 

Check pressure control range 

Summary of Contents for WNS Series

Page 1: ...l Gas fired Oil Boiler ZhangjiagangWilfordThermalTechnology Co Ltd Please read this manual carefully before using this machin Only qualified workers can operate this machine If the operation method is...

Page 2: ...ler structure 5 Boiler work principle 7 Operation Manual of Gas Fired Boiler 7 Operation requirements 7 Maintenance of boiler 11 Inspection hydraulic testing for pressure parts 12 Attention for users...

Page 3: ...appendix list product quality certificate one copy Installation description Preparation work before installation Check the completeness of the boiler accessories according to the packing list and the...

Page 4: ...drawings Water pump is connected with water tank if user has additional requirements can provide spare water pump 4 2 Safety valve must be assembled after hydraulic testing and connected to the tube f...

Page 5: ...r boiler water level indication and for the supervision by boiler operator The water level controller is used for transmitting the value of boiler water level The control system will control the runni...

Page 6: ...ecause of some reasons the photo resistance has no sense of light stop burning and send out acoustical light alarm continue post purging for gas fired boiler then stop running boiler Check and find ou...

Page 7: ...ill feed water into the boiler so as to keep it in the normal water level The above mentioned process continues steam will continuously produced by heating the water by absorbing the afterheat of firi...

Page 8: ...iler again according to above mentioned way Running boiler 3 1 Start and running boiler normally 3 1 1 Open the air vent valve on the top of boiler or lift the valve core of safety valve 3 1 2 Start b...

Page 9: ...warming tube should be according to the length diameter of pipeline steam temperature and so on In generally it should not less than ten minutes After the tube is heated open the main steam valve slow...

Page 10: ...it quality 6 9 The photoresistance should be removed for examination testing every three month measure the values of resistance of bright dark Photoresistance type MG41 100A Rated power capacity 100M...

Page 11: ...etter W means week Letter M means month Letter S means season Letter Y means year Blow down of boiler In generally the feeding water contains mineral matter when the water enters into boiler and after...

Page 12: ...nance if less than one month should use wet maintenance 4 1 Dry maintenance Stop running boiler drain off all boiler water remove all dirt inside boiler and clean it bake it by faint fire close all ha...

Page 13: ...ter dropping to working pressure During inspection the pressure should kept no change If find any leakage should well make record for later repairing when the pressure drop to atmosphere After hydraul...

Reviews: