LOOP 500
10
5.
Disable / enable operations
Disabling and re-enabling is possible as from the 2nd level.
5.1
Disabling and enabling zones and detectors
Disabling a detector
To disable a detector (e.g. No.12), the following keys should be pressed:
OFF
Zone
1
*
1
2
Steps carried out appear as follows on the display:
Z o n e X X X M l d Y Y
O F F
L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e Z o n e X X X M l d Y Y
T T T T T T T T T T T T
L 2 *
Disable
- indicates that disable has been carried out
TTT
..
- possible customer text (for detector No.12)
Indications
−
the DISABLE collective display illuminates
−
if operation of the control panel is disabled again by the key switch, the DISABLE LED will continue to be
actuated
Enabling a detector
In order to enable a detector (e.g. No.12) of a zone (e.g. No.1), the following keys should be pressed:
OFF
Zone
1
*
1
2
Steps carried out are shown on the display as follows:
Z o n e _ _ 1 M l d 1 2
O N
L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e E n d Z o n e 0 0 1 M l d 1 2
T T T T T T T T T T T T
L 2 *
Dis. end
- indicates that a disable operation has been terminated
TTT
..
- possible customer text (for detector No.12)
−
the DISABLE collective display only extinguishes when no further Disable is present in the control panel
http://www.firealarmengineers.com