LOOP 500
5
2.2.1.1. Measures in case of fire alarm in Night mode
−
Press Cancel int. aud. sign. key
The audible signal in the control panel will be muted
−
Initiate measures in accordance with alarm organization.
With more than two alarms active, the first and the last message will always appear on the display; all other
messages are concealed, this being indicated by the yellow ALARMS LED. The concealed messages can
only be scrolled after pressing the Reveal key at the ALARMS LED (in the field of the display); approx. 20
seconds after the arrow keys were last pressed, the first and the last message will be displayed again.
2.2.2.
Fire alarm in Day mode (systems with alarm delay function only)
A fire alarm in Day mode will be activated by an automatic fire detector when the control panel is in Day
mode.
Indications
−
1 red FIRE LED (in the centre) flashes
−
audible signal sounds continuously
−
on the display, the message as shown before appears
2.2.2.1. Measures in case of fire alarm in Day mode
−
Press Cancel int. aud. sign. key
The audible signal in the control panel will be muted.
the delay time is acknowledged and the investigation time started
−
Initiate measures in accordance with alarm organization.
The following message will appear on the display:
I n v e s t i g a t i o n i n p r o g r e s s
L 1 *
F Z Z Z
ZZZ - number of fire alarms active
2.3.
Pre-alarm
In the case of detector circuit double-knock operation or cross-zoning, on activation of the first detector or of
the first zone which is programmed in detector circuit double-knock operation or cross-zoning, a pre-alarm is
activated.
−
1 red FIRE LED (in the centre) flashes,
−
the audible signal sounds continuously,
the following message appears on the display:
P r e - a l a r m Z o n e X X X M l d Y Y
T T T T T T T T T T T T
L 1 *
F Z Z Z
XXX
- No. of the zone
YY
- No. of the detector
TTT
- possible customer text
ZZZ
- number of fire alarms active (where a pre-alarm is not counted as a fire alarm)
http://www.firealarmengineers.com