background image

                                                                                        LOOP 500

18

5.5.

Disabling and enabling the Fault main output

The Fault main output can be disabled and enabled manually by means of the Special Functions SF41 and
SF40.

Disabling the Fault main output

To disable the Fault main output, the following keys should be pressed:

ON

4

Special

functions

1

The ON/IN key is used here as Input key

The steps are shown on the display as follows:

                          S  p  e  c  i  a  l    f  u  n  c  t  .  4  1

L 2       *

Execution of the command is shown on the display as follows:

D  i  s  a  b  l  e    o  u  t  p  u  t    f  a  u  l  t

T T T T T T T T T T T T

L 2       *

Disable

- indicates that Disable has been carried out

TTT

- possible customer text (for Fault output)

Indications

 the DISABLE collective display illuminates

 if operation of the control panel is disabled again by means of the key switch, the DISABLE LED remains

activated

 
 

Enabling the Fault main output

To enable the Fault main output, the following keys should be pressed:

ON

4

Special

functions

0

The ON/IN key is used here as Input key

The steps carried out are shown on the display as follows:

                          S  p  e  c  i  a  l    f  u  n  c  t  .  4  0

L 2       *

http://www.firealarmengineers.com

Summary of Contents for LOOP 500

Page 1: ...LOOP 500 Fire Alarm System Operating instruction Part 1 217 647 Issue date 29 03 1995 TOTAL WALTHER GmbH Feuerschutz und Sicherheit http www firealarmengineers com...

Page 2: ...ays 19 7 Overview of special functions 19 8 Overview of fault messages 20 Operating instruction part 2 for the service people Page 9 Operation on the operator control level 3 3 9 1 Accessing the 3rd o...

Page 3: ...ble to cancel the internal audible signal to carry out the lamp test to display the alarm counter and to recall the concealed behind the display messages on the display Operator control level 2 The 2n...

Page 4: ...a fire alarm is activated by a non automatic fire detector automatic fire detector if the control panel is in Night mode only in the case of alarm delay function or is activated by a non automatic fi...

Page 5: ...y on the display the message as shown before appears 2 2 2 1 Measures in case of fire alarm in Day mode Press Cancel int aud sign key The audible signal in the control panel will be muted the delay ti...

Page 6: ...he display shows in plaintext the type of fault not in the case of system fault internal audible signal sounds intermittently in the case of system fault sounds continuously With more than one fault a...

Page 7: ...display and of the internal sounder will be carried out After approx 20 seconds the test is terminated automatically or manually with the C key 2 6 Displaying the alarm counter Press the Display key i...

Page 8: ...ay illumination will switch off the transmission unit will switch on automatically if not disabled from the control and indicating unit keyboard the DISABLE LED and FAULT DISABLE LED in the MASTER CON...

Page 9: ...ications 5 red FIRE LEDs flash internal audible signal sounds intermittently activation of the Fire main output is indicated by red ACTIVATION LED in the PRIMARY ALARM field yellow FIRE BRIGADE COMING...

Page 10: ...dications the DISABLE collective display illuminates if operation of the control panel is disabled again by the key switch the DISABLE LED will continue to be actuated Enabling a detector In order to...

Page 11: ...means the same thing in principle 5 2 Disabling enabling deactivating and activating controls 5 2 1 Disabling enabling controls Disabling a control The following keys should be pressed to disable a co...

Page 12: ...n t r o l 0 0 2 T T T T T T T T T T T T L 2 Dis end indicates that a Disable operation has been completed TTT possible customer text for Control No 2 the DISABLE collective display will only extinguis...

Page 13: ...F Control 1 Steps carried out are shown on the display as follows C o n t r o l _ _ 1 O F F L 2 Control 001 is deactivated Activation of a control To activate a control e g No 1 the following keys sho...

Page 14: ...LE LED in the EXT AUD ALARM DEVICE field illuminates the DISABLE collective display illuminates if operation of the control panel is disabled again by the key switch the DISABLE LED will continue to b...

Page 15: ...tes if operation of the control panel is disabled again by the key switch the DISABLE LED will continue to be actuated Enabling all alarm devices To enable all alarm devices the following key should b...

Page 16: ...ALARM DEVICE field extinguishes when all alarm devices are deactivated the alarm device e g Sounder 003 is deactivated Activation of an alarm device The following keys should be pressed to activate an...

Page 17: ...DISABLE LED will continue to be actuated Enabling the transmission unit Only a manually disabled transmission unit by means of the ON OFF key in the PRIMARY DETECTOR field can be enabled manually A tr...

Page 18: ...wn on the display as follows D i s a b l e o u t p u t f a u l t T T T T T T T T T T T T L 2 Disable indicates that Disable has been carried out TTT possible customer text for Fault output Indications...

Page 19: ...th No 00 To display the Event Memory the following keys should be pressed ON 2 Special functions 0 The ON IN key is used here as Input key Example of an event F i r e Z o n e 0 0 8 M l d 2 7 2 2 0 5 1...

Page 20: ...uses for the Main Outputs on the Motherboard 16 Fuses for the Parallel Control and Indicating Unit 17 Fuses for Control Lines 1 and 2 18 Fuses for Control Lines 3 and 4 19 Fuse for Relay Boards 1 12 2...

Page 21: ...H Feuerschutz und Sicherheit Waltherstra e 51 D 51069 Cologne Tel 02 21 67 85 0 Fax 02 21 67 85 207 A tyco INTERNATIONAL LTD COMPANY 217 647 7 97 No responsibility accepted for modifications or errors...

Reviews: