LOOP 500
18
5.5.
Disabling and enabling the Fault main output
The Fault main output can be disabled and enabled manually by means of the Special Functions SF41 and
SF40.
Disabling the Fault main output
To disable the Fault main output, the following keys should be pressed:
ON
4
Special
functions
1
The ON/IN key is used here as Input key
The steps are shown on the display as follows:
S p e c i a l f u n c t . 4 1
L 2 *
Execution of the command is shown on the display as follows:
D i s a b l e o u t p u t f a u l t
T T T T T T T T T T T T
L 2 *
Disable
- indicates that Disable has been carried out
TTT
- possible customer text (for Fault output)
Indications
−
the DISABLE collective display illuminates
−
if operation of the control panel is disabled again by means of the key switch, the DISABLE LED remains
activated
Enabling the Fault main output
To enable the Fault main output, the following keys should be pressed:
ON
4
Special
functions
0
The ON/IN key is used here as Input key
The steps carried out are shown on the display as follows:
S p e c i a l f u n c t . 4 0
L 2 *