7.
Premier MX Repeater Panel
User Controls [16 zone panel shown]
Switch Description
Functionality Button
Availability
Evacuate
Operates all sounders continuously and lights the Evacuated LED adjacent the
button until the silence button is operated
When controls are unlocked
Silence/Resound
Alarms
Following a fire alarm condition, 1st operation stops sounders. The General Fire
LED and the Zonal fire LED will change from flashing to steady. 2nd operation
restarts the previously silenced sounders
When controls are unlocked
Reset
Clears the panel display, resets the zones, outputs and operates the reset relay.
When controls are unlocked
and [if silence before reset is configured]
alarms silence switch has been operated.
1] Press to stop the buzzer sounding in fire or fault conditions.
When controls are locked or unlocked
Silence Buzzer
2] In 2 Stage Delay Mode, with stage 1 delay running, press to start stage 2
delay otherwise all delayed outputs operate when Stage 1 timer times out.
When the panel is in the fire condition and
the delay is running. Controls are locked
or unlocked
1] Press once to Enable the delay mode, lighting the adjacent delay on LED.
Press again to disable the delay mode and turn off the LED
1] When controls are unlocked
and delay
period is set to a value > 0.
Delay
On/Off/Override
2] Overrides the delay when delay is running, turning the delay mode and the
LED off. All delayed outputs will operate immediately.
2] When the panel is in the fire condition
and the delay is running.
Test Display
Press to illuminates all LEDs on the display and operate the buzzer. All
indications remain active for approx 5 seconds after button release.
When controls are locked or unlocked
8.
Routine Testing and maintenance
See Premier MX Log Book for details.
9.
User responsibilities
See Premier MX Log Book for details
Access Controls Keyswitch:
0 – Controls Locked
1 – Controls Unlocked