Written by:.JBJ
Checked by: RP
Document Number: Premier MX User 1.doc
Page 15 of 19
14/12/06
6.
Premier MX
Repeater Panel
User Operation - Fire and Fault Conditions
6.1.
If a fire is detected:
•
On the Premier MX
Repeater Panel:
o
The general Fire LED will flash and the buzzer will sound
o
The relevant zone Fire LED will flash, indicating the location of the
fire.
o
If the Delay is OFF [Delay LED off]:
The Fire Routing output and LED will operate immediately
The Fire Alarm sounders will operate immediately
The Fire Protection output will operate immediately
o
If the Delay is ON [Delay LED flashing]:
The Fire Routing output and LED will operate after a delay [if
the Fire Routing fault/disabled LED is illuminated].
The Fire Alarm sounders will operate after a delay [if Sounder
fault/disabled LED is illuminated].
The Fire Protection output will operate after a delay [if Fire
Protection fault/disabled LED is illuminated].
•
Locate the source of the fire alarm (an LED will be visible on the detector
which has been activated).
6.2.
To Silence the fire alarm sounders:
•
Turn the Access Controls Keyswitch on the repeater door to position “1”.
•
Press the Silence Alarms/Resound button once only.
•
The fire alarm sounders will become silent.
•
The General Fire LED and the Zone Fire LED will become steady.
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
6.3.
To Resound the fire alarm sounders after they have been silenced:
•
Turn the Access Controls Keyswitch on the repeater door to position “1”.
•
Press the Silence Alarms/Resound button once only.
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
6.4.
To Reset the panel & repeater(s) from a Fire Alarm:
•
After the fire has been extinguished, turn the Access Controls Keyswitch
on the repeater door to position “1”.
•
Press the Reset button.
•
The General Fire LED and the Zone Fire LED will clear.