Written by:.JBJ
Checked by: RP
Document Number: Premier MX User 1.doc
Page 12 of 19
14/12/06
•
To quit delay mode selection:
o
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
4.9.
To Override the Delay Mode
•
When the Delay is running:
o
The Delay On/Off LED will flash.
o
The general Fire and zone fire LEDs will flash.
o
The panel buzzer will operate.
•
Press the Delay On/Off/Override button while the Delay On/Off LED is
flashing to override the delay allowing all delayed outputs to operate
immediately.
4.10.
To Extend the Delay [from 1
st
stage to 2
nd
Stage]
•
When the panel is configured to the two stage delay mode and before 60
seconds has elapsed since the fire alarm triggered:
o
Press the Silence Buzzer button.
o
The Silence Buzzer button LED will light.
The buzzer will silence.
The 2
nd
stage delay will start.
4.11.
Silencing the Alarms During the Delay:
•
Turn the Access Controls Keyswitch on the panel door to position “1”.
•
Press the Silence Alarms/Resound button.
o
The General Fire LED and the Zone Fire LED become steady.
o
The sounders will not operate after the delay has timed out.
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
4.12.
Resounding the Alarms after the Delay: [Alarms previously silenced]
•
Turn the Access Controls Keyswitch on the panel door to position “1”.
•
Press the Silence Alarms/Resound button.
o
The General Fire LED will flash.
o
The sounders operate.
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.