Zeta Premier MX-16 User'S Operation Manual Download Page 17

Written by:.JBJ 

Checked by: RP 

Document Number: Premier MX User 1.doc 

Page 17 of 19 

14/12/06 

Premier MX

 

Repeater Panel Operation [16 zone version shown] 

General Indicator Section 

Indicator Description 

Indication 

Colour 

Operating Condition 

Power Supply On 

Green 

Steady indication for Mains or Standby power On. 

Fire 

Red 

Flashes on any new fire alarm condition, changing to a steady indication 
on operation of Silence Alarms. 

Fire Routing Active 

Red 

Steady indication when the Fire Routing Output is active. 

General Fault 

Yellow 

Flashes for any fault condition. 

Power Supply Fault 

Yellow 

Flashes for mains or standby power supply/charge fault 

System Fault 

Yellow 

Steady indication to indicate Microcontroller Failure. 

General Test 

Yellow

 

Steady indication when the zone or sounder test is active. 

General Disablement 

Yellow

 

Steady indication whilst a zone or output is disabled. 

Communications Fault 

Yellow

 

Flashes for a communications failure between the fire panel and repeater. 

Sounder Fault/Disabled 

Yellow 

Flashes for any sounder fault. Steady for sounders disabled. 

Sounder Test 

Yellow 

Steady indication while sounder walk test is active. 

Fire Protection Fault/Disabled 

Yellow 

Flashes for a fault on the Fire Protection Output. Steady when Fire 
Protection Output is disabled. 

Fire Routing Fault/Disabled 

Yellow 

Flashes for a fault on the Fire Routing Output. Steady when Fire Routing 
Output is disabled. 

Fault Routing Fault/Disabled 

Yellow 

Flashes for a fault on the Fault Routing Output. Steady when Fault 
Routing Output is disabled. 

 

 

 

 

 

 
 

Zone Location Indications 

Indicator Description 

Indication 

Colour 

Operating Condition 

User Generated Zone Location Text 

Red 

Flashes when zone is in a fire condition, turning to steady on 
operation of Silence Alarms. 

User Generated Zone Location Text 

Yellow 

Flashes when zone is in a fault condition. Illuminates steady when 
zone is disabled or in test. 

Access Controls 
Keyswitch: 

   0 – Controls Locked 
   1 – Controls Unlocked 

User Instructions

 

Summary of Contents for Premier MX-16

Page 1: ...7 4 3 To Disable Enable the Fire Routing Output 8 4 4 To Disable Enable the Fault Routing Output 8 4 5 To Disable Enable Fire Protection Output s 9 4 6 To Select Clear One Man Zone Test 10 4 7 To Sel...

Page 2: ...18 8 Routine Testing and maintenance 18 9 User responsibilities 18 10 Premier MX Isolate De isolate Test Mode Select Flowchart 19 Danger This equipment contains hazardous voltages that can cause deat...

Page 3: ...output will operate after a delay if Fire Protection fault disabled LED is illuminated Locate the source of the fire alarm an LED will be visible on the detector which has been activated 2 2 To Silenc...

Page 4: ...rm button to silence the fire alarm sounders and clear the Evacuate LED Set the Access Controls Keyswitch back to position 0 to lock the controls 2 6 If a fault is detected The panel buzzer will sound...

Page 5: ...tput Steady when Fault Routing Output is disabled 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 0 1 C E L No 1800456 32 ZONE FIRE POWER SUPPLY ON POWER SUPPLY...

Page 6: ...ed and if silence before reset is configured alarms silence switch has been operated 1 Press to stop the buzzer sounding in fire or fault conditions When controls are locked or unlocked Silence Buzzer...

Page 7: ...o The zone fault disabled LED will change to the Off flash indication while the cursor is on it changing to off if the cursor is moved on o The general Disablement LED will be cleared if no other disa...

Page 8: ...Fire Routing Output o Use the Select button to move the pulsed cursor indication up through the fault LEDs until it pulses the Fire Routing Fault Disabled LED The Select button moves the cursor down T...

Page 9: ...lement LED will be cleared if no other disablements are present To quit the disable enable mode o To exit the Select Mode press the Select On Off button o The Select On LED will clear o The cursor ind...

Page 10: ...rsor up To apply the test mode to the selected zone o Press the Test button to activate the test condition on the selected zone o The zone fault disabled LED will change to the On flash indication whi...

Page 11: ...no other circuits are in the test condition To quit test selection mode o To exit the Select Mode press the Select On Off button o The Select On LED will clear o The cursor indication will clear o Se...

Page 12: ...ill light The buzzer will silence The 2nd stage delay will start 4 11 Silencing the Alarms During the Delay Turn the Access Controls Keyswitch on the panel door to position 1 Press the Silence Alarms...

Page 13: ...elect Access Control key switch to position 1 Press the SELECT ON OFF switch Use the Up down keys to scroll the cursor LED indication through the selectable options on the panel display LEDs until the...

Page 14: ...et Display D N ON or D N OFF Change Change Pressing SELECT repeats the cursor display changes as above Pressing SELECT repeats the cursor display changes as above in reverse To exit Clock Module Menu...

Page 15: ...put will operate after a delay if Fire Protection fault disabled LED is illuminated Locate the source of the fire alarm an LED will be visible on the detector which has been activated 6 2 To Silence t...

Page 16: ...larm button to silence the fire alarm sounders and clear the Evacuate LED Set the Access Controls Keyswitch back to position 0 to lock the controls 6 6 If a fault is detected The repeater buzzer will...

Page 17: ...tions Fault Yellow Flashes for a communications failure between the fire panel and repeater Sounder Fault Disabled Yellow Flashes for any sounder fault Steady for sounders disabled Sounder Test Yellow...

Page 18: ...are locked or unlocked Silence Buzzer 2 In 2 Stage Delay Mode with stage 1 delay running press to start stage 2 delay otherwise all delayed outputs operate when Stage 1 timer times out When the panel...

Page 19: ...button Precepten Panel Selected Circuit returned to normal operation LED pulses OFF flash Changes to OFF when cursor is removed Press DISABLE button Precepten Panel Selected Circuit Disabled Circuit...

Reviews: