Written by:.JBJ
Checked by: RP
Document Number: Premier MX User 1.doc
Page 16 of 19
14/12/06
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
6.5.
To operate the fire alarm sounders in Evacuate Mode:
•
Turn the Access Controls Keyswitch on the repeater door to position “1”.
•
Press the Evacuate button.
•
The Evacuate LED will light and the repeater buzzer will operate.
•
All fire alarm sounders will operate.
•
Press the Silence/Resound Alarm button to silence the fire alarm sounders
and clear the Evacuate LED.
•
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
6.6.
If a fault is detected:
•
The repeater buzzer will sound.
•
The General Fault LED will flash.
•
One or more fault LEDs will flash; identifying which element of the
system is faulty.
•
When the fault is corrected the fault indication will clear automatically
unless the panel is configured to latched fault mode – in which case,
operating the Reset button will clear the fault indication.
6.7.
To Silence the Buzzer:
•
Press the Silence Buzzer button.
•
The Silence Buzzer button LED will light.
•
The buzzer will silence.